#include <GovHydroPelton.h>


Detailed hydro unit - Pelton model. This model can be used to represent the dynamic related to water tunnel and surge chamber. A schematic of the hydraulic system of detailed hydro unit models, like Francis and Pelton, is located under the GovHydroFrancis class.
| IEC61970::Base::Domain::Area IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::av0 | 
Area of the surge tank (AV0). Unit = m2. Typical Value = 30.
| IEC61970::Base::Domain::Area IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::av1 | 
Area of the compensation tank (AV1). Unit = m2. Typical Value = 700.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::bp | 
Droop (bp). Typical Value = 0.05.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::db1 | 
Intentional dead-band width (DB1). Unit = Hz. Typical Value = 0.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::db2 | 
Intentional dead-band width of valve opening error (DB2). Unit = Hz. Typical Value = 0.01.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::h1 | 
Head of compensation chamber water level with respect to the level of penstock (H1). Unit = m. Typical Value = 4.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::h2 | 
Head of surge tank water level with respect to the level of penstock (H2). Unit = m. Typical Value = 40.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::hn | 
Rated hydraulic head (Hn). Unit = m. Typical Value = 250.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::kc | 
Penstock loss coefficient (due to friction) (Kc). Typical Value = 0.025.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::kg | 
Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical Value = -0.025.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::qc0 | 
No-load turbine flow at nominal head (Qc0). Typical Value = 0.05.
| IEC61970::Base::Domain::VolumeFlowRate IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::qn | 
Rated flow (Qn). Unit = m3/s. Typical Value = 40.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::simplifiedPelton | 
Simplified Pelton model simulation (Sflag). true = enable of simplified Pelton model simulation false = enable of complete Pelton model simulation (non linear gain). Typical Value = false.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::staticCompensating | 
Static compensating characteristic (Cflag). true = enable of static compensating characteristic false = inhibit of static compensating characteristic. Typical Value = false.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::ta | 
Derivative gain (accelerometer time constant) (Ta). Typical Value = 3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::ts | 
Gate servo time constant (Ts). Typical Value = 0.15.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::tv | 
Servomotor integrator time constant (TV). Typical Value = 0.3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::twnc | 
Water inertia time constant (Twnc). Typical Value = 1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::twng | 
Water tunnel and surge chamber inertia time constant (Twng). Typical Value = 3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::tx | 
Electronic integrator time constant (Tx). Typical Value = 0.5.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::va | 
Maximum gate opening velocity (Va). Unit = PU/sec. Typical Value = 0.016.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::valvmax | 
Maximum gate opening (ValvMax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::valvmin | 
Minimum gate opening (ValvMin). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::vav | 
Maximum servomotor valve opening velocity (Vav). Typical Value = 0.017.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::vc | 
Maximum gate closing velocity (Vc). Unit = PU/sec. Typical Value = -0.016.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::vcv | 
Maximum servomotor valve closing velocity (Vcv). Typical Value = -0.017.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::waterTunnelSurgeChamberSimulation | 
Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical Value = false.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroPelton::zsfc | 
Head of upper water level with respect to the level of penstock (Zsfc). Unit = m. Typical Value = 25.
 1.8.13