#include <GovHydroFrancis.h>


Detailed hydro unit - Francis model. This model can be used to represent three types of governors. A schematic of the hydraulic system of detailed hydro unit models, like Francis and Pelton, is provided in the DetailedHydroModelHydraulicSystem diagram.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::am | 
Opening section Seff at the maximum efficiency (Am). Typical Value = 0.7.
| IEC61970::Base::Domain::Area IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::av0 | 
Area of the surge tank (AV0). Unit = m2. Typical Value = 30.
| IEC61970::Base::Domain::Area IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::av1 | 
Area of the compensation tank (AV1). Unit = m2. Typical Value = 700.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::bp | 
Droop (Bp). Typical Value = 0.05.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::db1 | 
Intentional dead-band width (DB1). Unit = Hz. Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::etamax | 
Maximum efficiency (EtaMax). Typical Value = 1.05.
| IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::FrancisGovernorControlKind IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::governorControl = IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::FrancisGovernorControlKind::_undef | 
Governor control flag (Cflag). Typical Value = mechanicHydrolicTachoAccelerator.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::h1 | 
Head of compensation chamber water level with respect to the level of penstock (H1). Unit = m. Typical Value = 4.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::h2 | 
Head of surge tank water level with respect to the level of penstock (H2). Unit = m. Typical Value = 40.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::hn | 
Rated hydraulic head (Hn). Unit = m. Typical Value = 250.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::kc | 
Penstock loss coefficient (due to friction) (Kc). Typical Value = 0.025.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::kg | 
Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical Value = 0.025.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::kt | 
Washout gain (Kt). Typical Value = 0.25.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::qc0 | 
No-load turbine flow at nominal head (Qc0). Typical Value = 0.21.
| IEC61970::Base::Domain::VolumeFlowRate IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::qn | 
Rated flow (Qn). Unit = m3/s. Typical Value = 40.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::ta | 
Derivative gain (Ta). Typical Value = 3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::td | 
Washout time constant (Td). Typical Value = 3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::ts | 
Gate servo time constant (Ts). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::twnc | 
Water inertia time constant (Twnc). Typical Value = 1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::twng | 
Water tunnel and surge chamber inertia time constant (Twng). Typical Value = 3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::tx | 
Derivative feedback gain (Tx). Typical Value = 1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::va | 
Maximum gate opening velocity (Va). Unit = PU/sec. Typical Value = 0.011.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::valvmax | 
Maximum gate opening (ValvMax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::valvmin | 
Minimum gate opening (ValvMin). Typical Value = 0.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::vc | 
Maximum gate closing velocity (Vc). Unit = PU/sec. Typical Value = -0.011.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::waterTunnelSurgeChamberSimulation | 
Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical Value = false.
| IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::zsfc | 
Head of upper water level with respect to the level of penstock (Zsfc). Unit = m. Typical Value = 25.
 1.8.13