IEC61970 17v23
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis Class Reference

#include <GovHydroFrancis.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU am
 
IEC61970::Base::Domain::Area av0
 
IEC61970::Base::Domain::Area av1
 
IEC61970::Base::Domain::PU bp
 
IEC61970::Base::Domain::Frequency db1
 
IEC61970::Base::Domain::PU etamax
 
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::FrancisGovernorControlKind governorControl = IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::FrancisGovernorControlKind::_undef
 
IEC61970::Base::Domain::Length h1
 
IEC61970::Base::Domain::Length h2
 
IEC61970::Base::Domain::Length hn
 
IEC61970::Base::Domain::PU kc
 
IEC61970::Base::Domain::PU kg
 
IEC61970::Base::Domain::PU kt
 
IEC61970::Base::Domain::PU qc0
 
IEC61970::Base::Domain::VolumeFlowRate qn
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds td
 
IEC61970::Base::Domain::Seconds ts
 
IEC61970::Base::Domain::Seconds twnc
 
IEC61970::Base::Domain::Seconds twng
 
IEC61970::Base::Domain::Seconds tx
 
IEC61970::Base::Domain::Float va
 
IEC61970::Base::Domain::PU valvmax
 
IEC61970::Base::Domain::PU valvmin
 
IEC61970::Base::Domain::Float vc
 
IEC61970::Base::Domain::Boolean waterTunnelSurgeChamberSimulation
 
IEC61970::Base::Domain::Length zsfc
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Detailed hydro unit - Francis model. This model can be used to represent three types of governors. A schematic of the hydraulic system of detailed hydro unit models, like Francis and Pelton, is provided in the DetailedHydroModelHydraulicSystem diagram.

Member Data Documentation

◆ am

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::am

Opening section Seff at the maximum efficiency (Am). Typical Value = 0.7.

◆ av0

IEC61970::Base::Domain::Area IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::av0

Area of the surge tank (AV0). Unit = m2. Typical Value = 30.

◆ av1

IEC61970::Base::Domain::Area IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::av1

Area of the compensation tank (AV1). Unit = m2. Typical Value = 700.

◆ bp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::bp

Droop (Bp). Typical Value = 0.05.

◆ db1

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::db1

Intentional dead-band width (DB1). Unit = Hz. Typical Value = 0.

◆ etamax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::etamax

Maximum efficiency (EtaMax). Typical Value = 1.05.

◆ governorControl

IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::FrancisGovernorControlKind IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::governorControl = IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::FrancisGovernorControlKind::_undef

Governor control flag (Cflag). Typical Value = mechanicHydrolicTachoAccelerator.

◆ h1

IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::h1

Head of compensation chamber water level with respect to the level of penstock (H1). Unit = m. Typical Value = 4.

◆ h2

IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::h2

Head of surge tank water level with respect to the level of penstock (H2). Unit = m. Typical Value = 40.

◆ hn

IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::hn

Rated hydraulic head (Hn). Unit = m. Typical Value = 250.

◆ kc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::kc

Penstock loss coefficient (due to friction) (Kc). Typical Value = 0.025.

◆ kg

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::kg

Water tunnel and surge chamber loss coefficient (due to friction) (Kg). Typical Value = 0.025.

◆ kt

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::kt

Washout gain (Kt). Typical Value = 0.25.

◆ qc0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::qc0

No-load turbine flow at nominal head (Qc0). Typical Value = 0.21.

◆ qn

IEC61970::Base::Domain::VolumeFlowRate IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::qn

Rated flow (Qn). Unit = m3/s. Typical Value = 40.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::ta

Derivative gain (Ta). Typical Value = 3.

◆ td

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::td

Washout time constant (Td). Typical Value = 3.

◆ ts

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::ts

Gate servo time constant (Ts). Typical Value = 0.5.

◆ twnc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::twnc

Water inertia time constant (Twnc). Typical Value = 1.

◆ twng

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::twng

Water tunnel and surge chamber inertia time constant (Twng). Typical Value = 3.

◆ tx

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::tx

Derivative feedback gain (Tx). Typical Value = 1.

◆ va

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::va

Maximum gate opening velocity (Va). Unit = PU/sec. Typical Value = 0.011.

◆ valvmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::valvmax

Maximum gate opening (ValvMax). Typical Value = 1.

◆ valvmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::valvmin

Minimum gate opening (ValvMin). Typical Value = 0.

◆ vc

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::vc

Maximum gate closing velocity (Vc). Unit = PU/sec. Typical Value = -0.011.

◆ waterTunnelSurgeChamberSimulation

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::waterTunnelSurgeChamberSimulation

Water tunnel and surge chamber simulation (Tflag). true = enable of water tunnel and surge chamber simulation false = inhibit of water tunnel and surge chamber simulation. Typical Value = false.

◆ zsfc

IEC61970::Base::Domain::Length IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroFrancis::zsfc

Head of upper water level with respect to the level of penstock (Zsfc). Unit = m. Typical Value = 25.


The documentation for this class was generated from the following files: