#include <SynchronousMachine.h>
An electromechanical device that operates with shaft rotating synchronously with the network. It is a single machine operating either as a generator or synchronous condenser or pump.
IEC61970::Base::Domain::Seconds IEC61970::Base::Wires::SynchronousMachine::aVRToManualLag |
Time delay required when switching from Automatic Voltage Regulation (AVR) to Manual for a lagging MVAr violation.
IEC61970::Base::Domain::Seconds IEC61970::Base::Wires::SynchronousMachine::aVRToManualLead |
Time delay required when switching from Automatic Voltage Regulation (AVR) to Manual for a leading MVAr violation.
IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::SynchronousMachine::baseQ |
Default base reactive power value. This value represents the initial reactive power that can be used by any application function.
IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::SynchronousMachine::condenserP |
Active power consumed when in condenser mode operation.
IEC61970::Base::Domain::Float IEC61970::Base::Wires::SynchronousMachine::coolantCondition |
Temperature or pressure of coolant medium
IEC61970::Base::Wires::CoolantType IEC61970::Base::Wires::SynchronousMachine::coolantType = IEC61970::Base::Wires::CoolantType::_undef |
Method of cooling the machine.
IEC61970::Base::Domain::Boolean IEC61970::Base::Wires::SynchronousMachine::earthing |
Indicates whether or not the generator is earthed. Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::SynchronousMachine::earthingStarPointR |
Generator star point earthing resistance (Re). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::SynchronousMachine::earthingStarPointX |
Generator star point earthing reactance (Xe). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::SynchronousMachine::ikk |
Steady-state short-circuit current (in A for the profile) of generator with compound excitation during 3-phase short circuit.
IEC61970::Base::Domain::Seconds IEC61970::Base::Wires::SynchronousMachine::manualToAVR |
Time delay required when switching from Manual to Automatic Voltage Regulation. This value is used in the accelerating power reference frame for powerflow solutions
IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::SynchronousMachine::maxQ |
Maximum reactive power limit. This is the maximum (nameplate) limit for the unit.
IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::SynchronousMachine::maxU |
Maximum voltage limit for the unit.
IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::SynchronousMachine::minQ |
Minimum reactive power limit for the unit.
IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::SynchronousMachine::minU |
Minimum voltage limit for the unit.
IEC61970::Base::Domain::Float IEC61970::Base::Wires::SynchronousMachine::mu |
Factor to calculate the breaking current (Section 4.5.2.1 in the IEC 60909-0). Used only for single fed short circuit on a generator (Section 4.3.4.2. in the IEC 60909-0).
IEC61970::Base::Wires::SynchronousMachineOperatingMode IEC61970::Base::Wires::SynchronousMachine::operatingMode = IEC61970::Base::Wires::SynchronousMachineOperatingMode::_undef |
Current mode of operation.
IEC61970::Base::Domain::PerCent IEC61970::Base::Wires::SynchronousMachine::qPercent |
Percent of the coordinated reactive control that comes from this machine.
IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::SynchronousMachine::r |
Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::SynchronousMachine::r0 |
Zero sequence resistance of the synchronous machine.
IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::SynchronousMachine::r2 |
Negative sequence resistance.
IEC61970::Base::Domain::Integer IEC61970::Base::Wires::SynchronousMachine::referencePriority |
Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.
IEC61970::Base::Domain::PU IEC61970::Base::Wires::SynchronousMachine::satDirectSubtransX |
Direct-axis subtransient reactance saturated, also known as Xd"sat.
IEC61970::Base::Domain::PU IEC61970::Base::Wires::SynchronousMachine::satDirectSyncX |
Direct-axes saturated synchronous reactance (xdsat); reciprocal of short- circuit ration. Used for short circuit data exchange, only for single fed short circuit on a generator. (Section 4.3.4.2. in the IEC 60909-0).
IEC61970::Base::Domain::PU IEC61970::Base::Wires::SynchronousMachine::satDirectTransX |
Saturated Direct-axis transient reactance. The attribute is primarily used for short circuit calculations according to ANSI.
IEC61970::Base::Wires::ShortCircuitRotorKind IEC61970::Base::Wires::SynchronousMachine::shortCircuitRotorType = IEC61970::Base::Wires::ShortCircuitRotorKind::_undef |
Type of rotor, used by short circuit applications, only for single fed short circuit according to IEC 60909.
IEC61970::Base::Wires::SynchronousMachineKind IEC61970::Base::Wires::SynchronousMachine::type = IEC61970::Base::Wires::SynchronousMachineKind::_undef |
Modes that this synchronous machine can operate in.
IEC61970::Base::Domain::PerCent IEC61970::Base::Wires::SynchronousMachine::voltageRegulationRange |
Range of generator voltage regulation (PG in the IEC 60909-0) used for calculation of the impedance correction factor KG defined in IEC 60909-0 This attribute is used to describe the operating voltage of the generating unit.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::SynchronousMachine::x0 |
Zero sequence reactance of the synchronous machine.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::SynchronousMachine::x2 |
Negative sequence reactance.