#include <WindPlantReactiveControlIEC.h>
Simplified plant voltage and reactive power control model for use with type 3 and type 4 wind turbine models.
Reference: IEC Standard 61400-27-1 Annex D.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::dxrefmax |
Maximum positive ramp rate for wind turbine reactive power/voltage reference (dxrefmax). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::dxrefmin |
Maximum negative ramp rate for wind turbine reactive power/voltage reference (dxrefmin). It is project dependent parameter.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kiwpx |
Plant Q controller integral gain (KIWPx). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kiwpxmax |
Maximum reactive Power/voltage reference from integration (KIWPxmax). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kiwpxmin |
Minimum reactive Power/voltage reference from integration (KIWPxmin). It is project dependent parameter.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kpwpx |
Plant Q controller proportional gain (KPWPx). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kwpqref |
Reactive power reference gain (KWPqref). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kwpqu |
Plant voltage control droop (KWPqu). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::tuqfilt |
Filter time constant for voltage dependent reactive power (Tuqfilt). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::twppfiltq |
Filter time constant for active power measurement (TWPpfiltq). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::twpqfiltq |
Filter time constant for reactive power measurement (TWPqfiltq). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::twpufiltq |
Filter time constant for voltage measurement (TWPufiltq). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::txft |
Lead time constant in reference value transfer function (Txft). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::txfv |
Lag time constant in reference value transfer function (Txfv). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::uwpqdip |
Voltage threshold for UVRT detection in q control (uWPqdip). It is project dependent parameter.
IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantQcontrolModeKind IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::windPlantQcontrolModesType = IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantQcontrolModeKind::_undef |
Reactive power/voltage controller mode (MWPqmode). It is case dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::xrefmax |
Maximum xWTref (qWTref or delta uWTref) request from the plant controller (xrefmax). It is case dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::xrefmin |
Minimum xWTref (qWTref or deltauWTref) request from the plant controller (xrefmin). It is project dependent parameter.