#include <WindContPType3IEC.h>
P control model Type 3.
Reference: IEC Standard 61400-27-1 Section 5.6.5.4.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dpmax |
Maximum wind turbine power ramp rate (dpmax). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dprefmax |
Maximum ramp rate of wind turbine reference power (dprefmax). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dprefmin |
Minimum ramp rate of wind turbine reference power (dprefmin). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dthetamax |
Ramp limitation of torque, required in some grid codes (dtmax). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dthetamaxuvrt |
Limitation of torque rise rate during UVRT (dthetamaxUVRT). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kdtd |
Gain for active drive train damping (KDTD). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kip |
PI controller integration parameter (KIp). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kpp |
PI controller proportional gain (KPp). It is type dependent parameter.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::mpuvrt |
Enable UVRT power control mode (MpUVRT). true = 1: voltage control false = 0: reactive power control. It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::omegaoffset |
Offset to reference value that limits controller action during rotor speed changes (omegaoffset). It is case dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::pdtdmax |
Maximum active drive train damping power (pDTDmax). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tdvs |
Time delay after deep voltage sags (TDVS). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::thetaemin |
Minimum electrical generator torque (temin). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::thetauscale |
Voltage scaling factor of reset-torque (tuscale). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tomegafiltp3 |
Filter time constant for generator speed measurement (Tomegafiltp3). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tpfiltp3 |
Filter time constant for power measurement (Tpfiltp3). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tpord |
Time constant in power order lag (Tpord). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tufiltp3 |
Filter time constant for voltage measurement (Tufiltp3). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::twref |
Time constant in speed reference filter (Tomega,ref). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::udvs |
Voltage limit for hold UVRT status after deep voltage sags (uDVS). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::updip |
Voltage dip threshold for P-control (uPdip). Part of turbine control, often different (e.g 0.8) from converter thresholds. It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::wdtd |
Active drive train damping frequency (omegaDTD). It can be calculated from two mass model parameters. It is type dependent parameter.
IEC61970::Dynamics::StandardModels::WindDynamics::WindTurbineType3IEC* IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::WindTurbineType3IEC |
Wind turbine type 3 model with which this Wind control P type 3 model is associated.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::zeta |
Coefficient for active drive train damping (zeta). It is type dependent parameter.