IEC61970 17v23
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4 Class Reference

#include <GovSteamFV4.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU cpsmn
 
IEC61970::Base::Domain::PU cpsmx
 
IEC61970::Base::Domain::PU crmn
 
IEC61970::Base::Domain::PU crmx
 
IEC61970::Base::Domain::PU kdc
 
IEC61970::Base::Domain::PU kf1
 
IEC61970::Base::Domain::PU kf3
 
IEC61970::Base::Domain::PU khp
 
IEC61970::Base::Domain::PU kic
 
IEC61970::Base::Domain::PU kip
 
IEC61970::Base::Domain::PU kit
 
IEC61970::Base::Domain::PU kmp1
 
IEC61970::Base::Domain::PU kmp2
 
IEC61970::Base::Domain::PU kpc
 
IEC61970::Base::Domain::PU kpp
 
IEC61970::Base::Domain::PU kpt
 
IEC61970::Base::Domain::PU krc
 
IEC61970::Base::Domain::PU ksh
 
IEC61970::Base::Domain::PU lpi
 
IEC61970::Base::Domain::PU lps
 
IEC61970::Base::Domain::PU mnef
 
IEC61970::Base::Domain::PU mxef
 
IEC61970::Base::Domain::PU pr1
 
IEC61970::Base::Domain::PU pr2
 
IEC61970::Base::Domain::PU psmn
 
IEC61970::Base::Domain::PU rsmimn
 
IEC61970::Base::Domain::PU rsmimx
 
IEC61970::Base::Domain::PU rvgmn
 
IEC61970::Base::Domain::PU rvgmx
 
IEC61970::Base::Domain::PU srmn
 
IEC61970::Base::Domain::PU srmx
 
IEC61970::Base::Domain::PU srsmp
 
IEC61970::Base::Domain::Float svmn
 
IEC61970::Base::Domain::Float svmx
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tam
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::Seconds tcm
 
IEC61970::Base::Domain::Seconds tdc
 
IEC61970::Base::Domain::Seconds tf1
 
IEC61970::Base::Domain::Seconds tf2
 
IEC61970::Base::Domain::Seconds thp
 
IEC61970::Base::Domain::Seconds tmp
 
IEC61970::Base::Domain::Seconds trh
 
IEC61970::Base::Domain::Seconds tv
 
IEC61970::Base::Domain::Seconds ty
 
IEC61970::Base::Domain::PU y
 
IEC61970::Base::Domain::PU yhpmn
 
IEC61970::Base::Domain::PU yhpmx
 
IEC61970::Base::Domain::PU ympmn
 
IEC61970::Base::Domain::PU ympmx
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Detailed electro-hydraulic governor for steam unit.

Member Data Documentation

◆ cpsmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::cpsmn

Minimum value of pressure regulator output (Cpsmn). Typical Value = -1.

◆ cpsmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::cpsmx

Maximum value of pressure regulator output (Cpsmx). Typical Value = 1.

◆ crmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::crmn

Minimum value of regulator set-point (Crmn). Typical Value = 0.

◆ crmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::crmx

Maximum value of regulator set-point (Crmx). Typical Value = 1.2.

◆ kdc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kdc

Derivative gain of pressure regulator (Kdc). Typical Value = 1.

◆ kf1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kf1

Frequency bias (reciprocal of droop) (Kf1). Typical Value = 20.

◆ kf3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kf3

Frequency control (reciprocal of droop) (Kf3). Typical Value = 20.

◆ khp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::khp

Fraction of total turbine output generated by HP part (Khp). Typical Value = 0.35.

◆ kic

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kic

Integral gain of pressure regulator (Kic). Typical Value = 0.0033.

◆ kip

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kip

Integral gain of pressure feedback regulator (Kip). Typical Value = 0.5.

◆ kit

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kit

Integral gain of electro-hydraulic regulator (Kit). Typical Value = 0.04.

◆ kmp1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kmp1

First gain coefficient of intercept valves characteristic (Kmp1). Typical Value = 0.5.

◆ kmp2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kmp2

Second gain coefficient of intercept valves characteristic (Kmp2). Typical Value = 3.5.

◆ kpc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kpc

Proportional gain of pressure regulator (Kpc). Typical Value = 0.5.

◆ kpp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kpp

Proportional gain of pressure feedback regulator (Kpp). Typical Value = 1.

◆ kpt

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::kpt

Proportional gain of electro-hydraulic regulator (Kpt). Typical Value = 0.3.

◆ krc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::krc

Maximum variation of fuel flow (Krc). Typical Value = 0.05.

◆ ksh

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::ksh

Pressure loss due to flow friction in the boiler tubes (Ksh). Typical Value = 0.08.

◆ lpi

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::lpi

Maximum negative power error (Lpi). Typical Value = -0.15.

◆ lps

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::lps

Maximum positive power error (Lps). Typical Value = 0.03.

◆ mnef

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::mnef

Lower limit for frequency correction (MNEF). Typical Value = -0.05.

◆ mxef

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::mxef

Upper limit for frequency correction (MXEF). Typical Value = 0.05.

◆ pr1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::pr1

First value of pressure set point static characteristic (Pr1). Typical Value = 0.2.

◆ pr2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::pr2

Second value of pressure set point static characteristic, corresponding to Ps0 = 1.0 PU (Pr2). Typical Value = 0.75.

◆ psmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::psmn

Minimum value of pressure set point static characteristic (Psmn). Typical Value = 1.

◆ rsmimn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::rsmimn

Minimum value of integral regulator (Rsmimn). Typical Value = 0.

◆ rsmimx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::rsmimx

Maximum value of integral regulator (Rsmimx). Typical Value = 1.1.

◆ rvgmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::rvgmn

Minimum value of integral regulator (Rvgmn). Typical Value = 0.

◆ rvgmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::rvgmx

Maximum value of integral regulator (Rvgmx). Typical Value = 1.2.

◆ srmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::srmn

Minimum valve opening (Srmn). Typical Value = 0.

◆ srmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::srmx

Maximum valve opening (Srmx). Typical Value = 1.1.

◆ srsmp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::srsmp

Intercept valves characteristic discontinuity point (Srsmp). Typical Value = 0. 43.

◆ svmn

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::svmn

Maximum regulator gate closing velocity (Svmn). Typical Value = -0.0333.

◆ svmx

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::svmx

Maximum regulator gate opening velocity (Svmx). Typical Value = 0.0333.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::ta

Control valves rate opening time (Ta). Typical Value = 0.8.

◆ tam

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tam

Intercept valves rate opening time (Tam). Typical Value = 0.8.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tc

Control valves rate closing time (Tc). Typical Value = 0.5.

◆ tcm

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tcm

Intercept valves rate closing time (Tcm). Typical Value = 0.5.

◆ tdc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tdc

Derivative time constant of pressure regulator (Tdc). Typical Value = 90.

◆ tf1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tf1

Time constant of fuel regulation (Tf1). Typical Value = 10.

◆ tf2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tf2

Time constant of steam chest (Tf2). Typical Value = 10.

◆ thp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::thp

High pressure (HP) time constant of the turbine (Thp). Typical Value = 0.15.

◆ tmp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tmp

Low pressure (LP) time constant of the turbine (Tmp). Typical Value = 0.4.

◆ trh

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::trh

Reheater time constant of the turbine (Trh). Typical Value = 10.

◆ tv

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::tv

Boiler time constant (Tv). Typical Value = 60.

◆ ty

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::ty

Control valves servo time constant (Ty). Typical Value = 0.1.

◆ y

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::y

Coefficient of linearized equations of turbine (Stodola formulation) (Y). Typical Value = 0.13.

◆ yhpmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::yhpmn

Minimum control valve position (Yhpmn). Typical Value = 0.

◆ yhpmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::yhpmx

Maximum control valve position (Yhpmx). Typical Value = 1.1.

◆ ympmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::ympmn

Minimum intercept valve position (Ympmn). Typical Value = 0.

◆ ympmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV4::ympmx

Maximum intercept valve position (Ympmx). Typical Value = 1.1.


The documentation for this class was generated from the following files: