IEC61970 17v23
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3 Class Reference

#include <GovSteamFV3.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU k
 
IEC61970::Base::Domain::PU k1
 
IEC61970::Base::Domain::PU k2
 
IEC61970::Base::Domain::PU k3
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::PU pmax
 
IEC61970::Base::Domain::PU pmin
 
IEC61970::Base::Domain::PU prmax
 
IEC61970::Base::Domain::Seconds t1
 
IEC61970::Base::Domain::Seconds t2
 
IEC61970::Base::Domain::Seconds t3
 
IEC61970::Base::Domain::Seconds t4
 
IEC61970::Base::Domain::Seconds t5
 
IEC61970::Base::Domain::Seconds t6
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tb
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::Float uc
 
IEC61970::Base::Domain::Float uo
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Simplified GovSteamIEEE1 Steam turbine governor model with Prmax limit and fast valving.

Member Data Documentation

◆ k

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k

Governor gain, (reciprocal of droop) (K). Typical Value = 20.

◆ k1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k1

Fraction of turbine power developed after first boiler pass (K1). Typical Value = 0.2.

◆ k2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k2

Fraction of turbine power developed after second boiler pass (K2). Typical Value = 0.2.

◆ k3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k3

Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical Value = 0.6.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::mwbase

Base for power values (MWbase) (>0). Unit = MW.

◆ pmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::pmax

Maximum valve opening, PU of MWbase (Pmax). Typical Value = 1.

◆ pmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::pmin

Minimum valve opening, PU of MWbase (Pmin). Typical Value = 0.

◆ prmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::prmax

Max. pressure in reheater (Prmax). Typical Value = 1.

◆ t1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t1

Governor lead time constant (T1). Typical Value = 0.

◆ t2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t2

Governor lag time constant (T2). Typical Value = 0.

◆ t3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t3

Valve positioner time constant (T3). Typical Value = 0.

◆ t4

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t4

Inlet piping/steam bowl time constant (T4). Typical Value = 0.2.

◆ t5

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t5

Time constant of second boiler pass (i.e. reheater) (T5). Typical Value = 0.5.

◆ t6

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t6

Time constant of crossover or third boiler pass (T6). Typical Value = 10.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::ta

Time to close intercept valve (IV) (Ta). Typical Value = 0.97.

◆ tb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::tb

Time until IV starts to reopen (Tb). Typical Value = 0.98.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::tc

Time until IV is fully open (Tc). Typical Value = 0.99.

◆ uc

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::uc

Maximum valve closing velocity (Uc). Unit = PU/sec. Typical Value = -1.

◆ uo

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::uo

Maximum valve opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1.


The documentation for this class was generated from the following files: