#include <GovSteamFV3.h>


Simplified GovSteamIEEE1 Steam turbine governor model with Prmax limit and fast valving.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k | 
Governor gain, (reciprocal of droop) (K). Typical Value = 20.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k1 | 
Fraction of turbine power developed after first boiler pass (K1). Typical Value = 0.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k2 | 
Fraction of turbine power developed after second boiler pass (K2). Typical Value = 0.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::k3 | 
Fraction of hp turbine power developed after crossover or third boiler pass (K3). Typical Value = 0.6.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::mwbase | 
Base for power values (MWbase) (>0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::pmax | 
Maximum valve opening, PU of MWbase (Pmax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::pmin | 
Minimum valve opening, PU of MWbase (Pmin). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::prmax | 
Max. pressure in reheater (Prmax). Typical Value = 1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t1 | 
Governor lead time constant (T1). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t2 | 
Governor lag time constant (T2). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t3 | 
Valve positioner time constant (T3). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t4 | 
Inlet piping/steam bowl time constant (T4). Typical Value = 0.2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t5 | 
Time constant of second boiler pass (i.e. reheater) (T5). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::t6 | 
Time constant of crossover or third boiler pass (T6). Typical Value = 10.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::ta | 
Time to close intercept valve (IV) (Ta). Typical Value = 0.97.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::tb | 
Time until IV starts to reopen (Tb). Typical Value = 0.98.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::tc | 
Time until IV is fully open (Tc). Typical Value = 0.99.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::uc | 
Maximum valve closing velocity (Uc). Unit = PU/sec. Typical Value = -1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamFV3::uo | 
Maximum valve opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1.