#include <GovSteamEU.h>


Simplified model of boiler and steam turbine with PID governor.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::chc | 
Control valves rate closing limit (Chc). Unit = PU/sec. Typical Value = -3.3.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::cho | 
Control valves rate opening limit (Cho). Unit = PU/sec. Typical Value = 0.17.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::cic | 
Intercept valves rate closing limit (Cic). Typical Value = -2.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::cio | 
Intercept valves rate opening limit (Cio). Typical Value = 0.123.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::db1 | 
Dead band of the frequency corrector (db1). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::db2 | 
Dead band of the speed governor (db2). Typical Value = 0.0004.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::hhpmax | 
Maximum control valve position (Hhpmax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::ke | 
Gain of the power controller (Ke). Typical Value = 0.65.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::kfcor | 
Gain of the frequency corrector (Kfcor). Typical Value = 20.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::khp | 
Fraction of total turbine output generated by HP part (Khp). Typical Value = 0. 277.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::klp | 
Fraction of total turbine output generated by HP part (Klp). Typical Value = 0. 723.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::kwcor | 
Gain of the speed governor (Kwcor). Typical Value = 20.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::mwbase | 
Base for power values (MWbase) (>0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::pmax | 
Maximal active power of the turbine (Pmax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::prhmax | 
Maximum low pressure limit (Prhmax). Typical Value = 1.4.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::simx | 
Intercept valves transfer limit (Simx). Typical Value = 0.425.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tb | 
Boiler time constant (Tb). Typical Value = 100.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tdp | 
Derivative time constant of the power controller (Tdp). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::ten | 
Electro hydraulic transducer (Ten). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tf | 
Frequency transducer time constant (Tf). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tfp | 
Time constant of the power controller (Tfp). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::thp | 
High pressure (HP) time constant of the turbine (Thp). Typical Value = 0.31.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tip | 
Integral time constant of the power controller (Tip). Typical Value = 2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tlp | 
Low pressure(LP) time constant of the turbine (Tlp). Typical Value = 0.45.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tp | 
Power transducer time constant (Tp). Typical Value = 0.07.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::trh | 
Reheater time constant of the turbine (Trh). Typical Value = 8.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tvhp | 
Control valves servo time constant (Tvhp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tvip | 
Intercept valves servo time constant (Tvip). Typical Value = 0.15.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tw | 
Speed transducer time constant (Tw). Typical Value = 0.02.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wfmax | 
Upper limit for frequency correction (Wfmax). Typical Value = 0.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wfmin | 
Lower limit for frequency correction (Wfmin). Typical Value = -0.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wmax1 | 
Emergency speed control lower limit (wmax1). Typical Value = 1.025.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wmax2 | 
Emergency speed control upper limit (wmax2). Typical Value = 1.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wwmax | 
Upper limit for the speed governor (Wwmax). Typical Value = 0.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wwmin | 
Lower limit for the speed governor frequency correction (Wwmin). Typical Value = -1.