#include <GovSteamCC.h>


Cross compound turbine governor model.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::dhp | 
HP damping factor (Dhp). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::dlp | 
LP damping factor (Dlp). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::fhp | 
Fraction of HP power ahead of reheater (Fhp). Typical Value = 0.3.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::flp | 
Fraction of LP power ahead of reheater (Flp). Typical Value = 0.7.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::mwbase | 
Base for power values (MWbase) (>0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::pmaxhp | 
Maximum HP value position (Pmaxhp). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::pmaxlp | 
Maximum LP value position (Pmaxlp). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::rhp | 
HP governor droop (Rhp). Typical Value = 0.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::rlp | 
LP governor droop (Rlp). Typical Value = 0.05.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t1hp | 
HP governor time constant (T1hp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t1lp | 
LP governor time constant (T1lp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t3hp | 
HP turbine time constant (T3hp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t3lp | 
LP turbine time constant (T3lp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t4hp | 
HP turbine time constant (T4hp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t4lp | 
LP turbine time constant (T4lp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t5hp | 
HP reheater time constant (T5hp). Typical Value = 10.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t5lp | 
LP reheater time constant (T5lp). Typical Value = 10.
 1.8.13
 1.8.13