#include <GovHydroWEH.h>


Woodward Electric Hydro Governor Model.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::db | 
Speed Dead Band (db).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::dicn | 
Value to allow the integral controller to advance beyond the gate limits (Dicn).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::dpv | 
Value to allow the Pilot valve controller to advance beyond the gate limits (Dpv).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::dturb | 
Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU).
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::feedbackSignal | 
Feedback signal selection (Sw). true = PID Output (if R-Perm-Gate=droop and R-Perm-Pe=0) false = Electrical Power (if R-Perm-Gate=0 and R-Perm-Pe=droop) or false = Gate Position (if R-Perm-Gate=droop and R-Perm-Pe=0).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fl1 | 
Flow Gate 1 (Fl1). Flow value for gate position point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fl2 | 
Flow Gate 2 (Fl2). Flow value for gate position point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fl3 | 
Flow Gate 3 (Fl3). Flow value for gate position point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fl4 | 
Flow Gate 4 (Fl4). Flow value for gate position point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fl5 | 
Flow Gate 5 (Fl5). Flow value for gate position point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp1 | 
Flow P1 (Fp1). Turbine Flow value for point 1 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp10 | 
Flow P10 (Fp10). Turbine Flow value for point 10 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp2 | 
Flow P2 (Fp2). Turbine Flow value for point 2 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp3 | 
Flow P3 (Fp3). Turbine Flow value for point 3 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp4 | 
Flow P4 (Fp4). Turbine Flow value for point 4 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp5 | 
Flow P5 (Fp5). Turbine Flow value for point 5 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp6 | 
Flow P6 (Fp6). Turbine Flow value for point 6 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp7 | 
Flow P7 (Fp7). Turbine Flow value for point 7 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp8 | 
Flow P8 (Fp8). Turbine Flow value for point 8 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::fp9 | 
Flow P9 (Fp9). Turbine Flow value for point 9 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gmax | 
Maximum Gate Position (Gmax).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gmin | 
Minimum Gate Position (Gmin).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gtmxcl | 
Maximum gate closing rate (Gtmxcl).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gtmxop | 
Maximum gate opening rate (Gtmxop).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gv1 | 
Gate 1 (Gv1). Gate Position value for point 1 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gv2 | 
Gate 2 (Gv2). Gate Position value for point 2 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gv3 | 
Gate 3 (Gv3). Gate Position value for point 3 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gv4 | 
Gate 4 (Gv4). Gate Position value for point 4 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::gv5 | 
Gate 5 (Gv5). Gate Position value for point 5 for lookup table representing water flow through the turbine as a function of gate position to produce steady state flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::kd | 
Derivative controller derivative gain (Kd).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::ki | 
Derivative controller Integral gain (Ki).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::kp | 
Derivative control gain (Kp).
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::mwbase | 
Base for power values (MWbase) (>0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss1 | 
Pmss Flow P1 (Pmss1). Mechanical Power output Pmss for Turbine Flow point 1 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss10 | 
Pmss Flow P10 (Pmss10). Mechanical Power output Pmss for Turbine Flow point 10 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss2 | 
Pmss Flow P2 (Pmss2). Mechanical Power output Pmss for Turbine Flow point 2 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss3 | 
Pmss Flow P3 (Pmss3). Mechanical Power output Pmss for Turbine Flow point 3 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss4 | 
Pmss Flow P4 (Pmss4). Mechanical Power output Pmss for Turbine Flow point 4 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss5 | 
Pmss Flow P5 (Pmss5). Mechanical Power output Pmss for Turbine Flow point 5 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss6 | 
Pmss Flow P6 (Pmss6). Mechanical Power output Pmss for Turbine Flow point 6 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss7 | 
Pmss Flow P7 (Pmss7). Mechanical Power output Pmss for Turbine Flow point 7 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss8 | 
Pmss Flow P8 (Pmss8). Mechanical Power output Pmss for Turbine Flow point 8 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::pmss9 | 
Pmss Flow P9 (Pmss9). Mechanical Power output Pmss for Turbine Flow point 9 for lookup table representing per unit mechanical power on machine MVA rating as a function of turbine flow.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::rpg | 
Permanent droop for governor output feedback (R-Perm-Gate).
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::rpp | 
Permanent droop for electrical power feedback (R-Perm-Pe).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::td | 
Derivative controller time constant to limit the derivative characteristic beyond a breakdown frequency to avoid amplification of high-frequency noise (Td).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::tdv | 
Distributive Valve time lag time constant (Tdv).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::tg | 
Value to allow the Distribution valve controller to advance beyond the gate movement rate limit (Tg).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::tp | 
Pilot Valve time lag time constant (Tp).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::tpe | 
Electrical power droop time constant (Tpe).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWEH::tw | 
Water inertia time constant (Tw) (>0).
 1.8.13