#include <GovHydroIEEE2.h>


IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors.
Ref<font color="#0f0f0f">erence: IEEE Transactions on Power Apparatus and Systems</font> <font color="#0f0f0f">November/December 1973, Volume PAS-92, Number 6</font> <font color="#0f0f0f"><u>Dynamic Models for Steam and Hydro Turbines in Power System Studies</u>, Page 1904.</font>
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::aturb | 
Turbine numerator multiplier (Aturb). Typical Value = -1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::bturb | 
Turbine denominator multiplier (Bturb). Typical Value = 0.5.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::gv1 | 
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::gv2 | 
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::gv3 | 
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::gv4 | 
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::gv5 | 
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::gv6 | 
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::kturb | 
Turbine gain (Kturb). Typical Value = 1.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::mwbase | 
Base for power values (MWbase) (> 0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pgv1 | 
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pgv2 | 
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pgv3 | 
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pgv4 | 
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pgv5 | 
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pgv6 | 
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pmax | 
Maximum gate opening (Pmax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::pmin | 
Minimum gate opening (Pmin). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::rperm | 
Permanent droop (Rperm). Typical Value = 0.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::rtemp | 
Temporary droop (Rtemp). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::tg | 
Gate servo time constant (Tg). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::tp | 
Pilot servo valve time constant (Tp). Typical Value = 0.03.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::tr | 
Dashpot time constant (Tr). Typical Value = 12.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::tw | 
Water inertia time constant (Tw). Typical Value = 2.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::uc | 
Maximum gate closing velocity (Uc) (<0). Typical Value = -0.1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroIEEE2::uo | 
Maximum gate opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1.
 1.8.13