#include <GovHydro4.h>


Hydro turbine and governor. Represents plants with straight-forward penstock configurations and hydraulic governors of traditional 'dashpot' type. This model can be used to represent simple, Francis, Pelton or Kaplan turbines.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::at | 
Turbine gain (At). Typical Value = 1.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv0 | 
Kaplan blade servo point 0 (Bgv0). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv1 | 
Kaplan blade servo point 1 (Bgv1). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv2 | 
Kaplan blade servo point 2 (Bgv2). Typical Value = 0. Typical Value Francis = 0, Kaplan = 0.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv3 | 
Kaplan blade servo point 3 (Bgv3). Typical Value = 0. Typical Value Francis = 0, Kaplan = 0.667.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv4 | 
Kaplan blade servo point 4 (Bgv4). Typical Value = 0. Typical Value Francis = 0, Kaplan = 0.9.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv5 | 
Kaplan blade servo point 5 (Bgv5). Typical Value = 0. Typical Value Francis = 0, Kaplan = 1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bmax | 
Maximum blade adjustment factor (Bmax). Typical Value = 0. Typical Value Francis = 0, Kaplan = 1.1276.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::db1 | 
Intentional deadband width (db1). Unit = Hz. Typical Value = 0.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::db2 | 
Unintentional dead-band (db2). Unit = MW. Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::dturb | 
Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU). Typical Value = 0.5. Typical Value Francis = 1.1, Kaplan = 1.1.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::eps | 
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gmax | 
Maximum gate opening, PU of MWbase (Gmax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gmin | 
Minimum gate opening, PU of MWbase (Gmin). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv0 | 
Nonlinear gain point 0, PU gv (Gv0). Typical Value = 0. Typical Value Francis = 0.1, Kaplan = 0.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv1 | 
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0. Typical Value Francis = 0.4, Kaplan = 0.4.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv2 | 
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0. Typical Value Francis = 0.5, Kaplan = 0.5.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv3 | 
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0. Typical Value Francis = 0.7, Kaplan = 0.7.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv4 | 
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0. Typical Value Francis = 0.8, Kaplan = 0.8.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv5 | 
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0. Typical Value Francis = 0.9, Kaplan = 0.9.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::hdam | 
Head available at dam (hdam). Typical Value = 1.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::mwbase | 
Base for power values (MWbase) (>0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv0 | 
Nonlinear gain point 0, PU power (Pgv0). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv1 | 
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0. Typical Value Francis = 0.42, Kaplan = 0.35.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv2 | 
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0. Typical Value Francis = 0.56, Kaplan = 0.468.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv3 | 
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0. Typical Value Francis = 0.8, Kaplan = 0.796.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv4 | 
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0. Typical Value Francis = 0.9, Kaplan = 0.917.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv5 | 
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0. Typical Value Francis = 0.97, Kaplan = 0.99.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::qn1 | 
No-load flow at nominal head (Qnl). Typical Value = 0.08. Typical Value Francis = 0, Kaplan = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::rperm | 
Permanent droop (Rperm). Typical Value = 0.05.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::rtemp | 
Temporary droop (Rtemp). Typical Value = 0.3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tblade | 
Blade servo time constant (Tblade). Typical Value = 100.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tg | 
Gate servo time constant (Tg) (>0). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tp | 
Pilot servo time constant (Tp). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tr | 
Dashpot time constant (Tr) (>0). Typical Value = 5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tw | 
Water inertia time constant (Tw) (>0). Typical Value = 1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::uc | 
Max gate closing velocity (Uc). Typical Value = 0.2.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::uo | 
Max gate opening velocity (Uo). Typical Value = 0.2.
 1.8.13