IEC61970 17v23
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4 Class Reference

#include <GovHydro4.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU at
 
IEC61970::Base::Domain::PU bgv0
 
IEC61970::Base::Domain::PU bgv1
 
IEC61970::Base::Domain::PU bgv2
 
IEC61970::Base::Domain::PU bgv3
 
IEC61970::Base::Domain::PU bgv4
 
IEC61970::Base::Domain::PU bgv5
 
IEC61970::Base::Domain::Float bmax
 
IEC61970::Base::Domain::Frequency db1
 
IEC61970::Base::Domain::ActivePower db2
 
IEC61970::Base::Domain::PU dturb
 
IEC61970::Base::Domain::Frequency eps
 
IEC61970::Base::Domain::PU gmax
 
IEC61970::Base::Domain::PU gmin
 
IEC61970::Base::Domain::PU gv0
 
IEC61970::Base::Domain::PU gv1
 
IEC61970::Base::Domain::PU gv2
 
IEC61970::Base::Domain::PU gv3
 
IEC61970::Base::Domain::PU gv4
 
IEC61970::Base::Domain::PU gv5
 
IEC61970::Base::Domain::PU hdam
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::PU pgv0
 
IEC61970::Base::Domain::PU pgv1
 
IEC61970::Base::Domain::PU pgv2
 
IEC61970::Base::Domain::PU pgv3
 
IEC61970::Base::Domain::PU pgv4
 
IEC61970::Base::Domain::PU pgv5
 
IEC61970::Base::Domain::PU qn1
 
IEC61970::Base::Domain::Seconds rperm
 
IEC61970::Base::Domain::Seconds rtemp
 
IEC61970::Base::Domain::Seconds tblade
 
IEC61970::Base::Domain::Seconds tg
 
IEC61970::Base::Domain::Seconds tp
 
IEC61970::Base::Domain::Seconds tr
 
IEC61970::Base::Domain::Seconds tw
 
IEC61970::Base::Domain::Float uc
 
IEC61970::Base::Domain::Float uo
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Hydro turbine and governor. Represents plants with straight-forward penstock configurations and hydraulic governors of traditional 'dashpot' type. This model can be used to represent simple, Francis, Pelton or Kaplan turbines.

Member Data Documentation

◆ at

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::at

Turbine gain (At). Typical Value = 1.2.

◆ bgv0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv0

Kaplan blade servo point 0 (Bgv0). Typical Value = 0.

◆ bgv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv1

Kaplan blade servo point 1 (Bgv1). Typical Value = 0.

◆ bgv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv2

Kaplan blade servo point 2 (Bgv2). Typical Value = 0. Typical Value Francis = 0, Kaplan = 0.1.

◆ bgv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv3

Kaplan blade servo point 3 (Bgv3). Typical Value = 0. Typical Value Francis = 0, Kaplan = 0.667.

◆ bgv4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv4

Kaplan blade servo point 4 (Bgv4). Typical Value = 0. Typical Value Francis = 0, Kaplan = 0.9.

◆ bgv5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bgv5

Kaplan blade servo point 5 (Bgv5). Typical Value = 0. Typical Value Francis = 0, Kaplan = 1.

◆ bmax

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::bmax

Maximum blade adjustment factor (Bmax). Typical Value = 0. Typical Value Francis = 0, Kaplan = 1.1276.

◆ db1

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::db1

Intentional deadband width (db1). Unit = Hz. Typical Value = 0.

◆ db2

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::db2

Unintentional dead-band (db2). Unit = MW. Typical Value = 0.

◆ dturb

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::dturb

Turbine damping factor (Dturb). Unit = delta P (PU of MWbase) / delta speed (PU). Typical Value = 0.5. Typical Value Francis = 1.1, Kaplan = 1.1.

◆ eps

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::eps

Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.

◆ gmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gmax

Maximum gate opening, PU of MWbase (Gmax). Typical Value = 1.

◆ gmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gmin

Minimum gate opening, PU of MWbase (Gmin). Typical Value = 0.

◆ gv0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv0

Nonlinear gain point 0, PU gv (Gv0). Typical Value = 0. Typical Value Francis = 0.1, Kaplan = 0.1.

◆ gv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv1

Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0. Typical Value Francis = 0.4, Kaplan = 0.4.

◆ gv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv2

Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0. Typical Value Francis = 0.5, Kaplan = 0.5.

◆ gv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv3

Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0. Typical Value Francis = 0.7, Kaplan = 0.7.

◆ gv4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv4

Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0. Typical Value Francis = 0.8, Kaplan = 0.8.

◆ gv5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::gv5

Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0. Typical Value Francis = 0.9, Kaplan = 0.9.

◆ hdam

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::hdam

Head available at dam (hdam). Typical Value = 1.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::mwbase

Base for power values (MWbase) (>0). Unit = MW.

◆ pgv0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv0

Nonlinear gain point 0, PU power (Pgv0). Typical Value = 0.

◆ pgv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv1

Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0. Typical Value Francis = 0.42, Kaplan = 0.35.

◆ pgv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv2

Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0. Typical Value Francis = 0.56, Kaplan = 0.468.

◆ pgv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv3

Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0. Typical Value Francis = 0.8, Kaplan = 0.796.

◆ pgv4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv4

Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0. Typical Value Francis = 0.9, Kaplan = 0.917.

◆ pgv5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::pgv5

Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0. Typical Value Francis = 0.97, Kaplan = 0.99.

◆ qn1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::qn1

No-load flow at nominal head (Qnl). Typical Value = 0.08. Typical Value Francis = 0, Kaplan = 0.

◆ rperm

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::rperm

Permanent droop (Rperm). Typical Value = 0.05.

◆ rtemp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::rtemp

Temporary droop (Rtemp). Typical Value = 0.3.

◆ tblade

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tblade

Blade servo time constant (Tblade). Typical Value = 100.

◆ tg

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tg

Gate servo time constant (Tg) (>0). Typical Value = 0.5.

◆ tp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tp

Pilot servo time constant (Tp). Typical Value = 0.1.

◆ tr

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tr

Dashpot time constant (Tr) (>0). Typical Value = 5.

◆ tw

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::tw

Water inertia time constant (Tw) (>0). Typical Value = 1.

◆ uc

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::uc

Max gate closing velocity (Uc). Typical Value = 0.2.

◆ uo

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro4::uo

Max gate opening velocity (Uo). Typical Value = 0.2.


The documentation for this class was generated from the following files: