#include <GovHydro2.h>


IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::aturb | 
Turbine numerator multiplier (Aturb). Typical Value = -1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::bturb | 
Turbine denominator multiplier (Bturb). Typical Value = 0.5.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::db1 | 
Intentional deadband width (db1). Unit = Hz. Typical Value = 0.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::db2 | 
Unintentional deadband (db2). Unit = MW. Typical Value = 0.
| IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::eps | 
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv1 | 
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv2 | 
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv3 | 
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv4 | 
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv5 | 
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv6 | 
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::kturb | 
Turbine gain (Kturb). Typical Value = 1.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::mwbase | 
Base for power values (MWbase) (> 0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv1 | 
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv2 | 
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv3 | 
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv4 | 
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv5 | 
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv6 | 
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pmax | 
Maximum gate opening (Pmax). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pmin | 
Minimum gate opening; (Pmin). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::rperm | 
Permanent droop (Rperm). Typical Value = 0.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::rtemp | 
Temporary droop (Rtemp). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tg | 
Gate servo time constant (Tg). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tp | 
Pilot servo valve time constant (Tp). Typical Value = 0.03.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tr | 
Dashpot time constant (Tr). Typical Value = 12.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tw | 
Water inertia time constant (Tw). Typical Value = 2.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::uc | 
Maximum gate closing velocity (Uc) (<0). Unit = PU/sec. Typical Value = -0.1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::uo | 
Maximum gate opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1.
 1.8.13
 1.8.13