#include <GovHydro1.h>


Basic Hydro turbine governor model.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::at | 
Turbine gain (At) (>0). Typical Value = 1.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::dturb | 
Turbine damping factor (Dturb) (>=0). Typical Value = 0.5.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::gmax | 
Maximum gate opening (Gmax) (>0). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::gmin | 
Minimum gate opening (Gmin) (>=0). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::hdam | 
Turbine nominal head (hdam). Typical Value = 1.
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::mwbase | 
Base for power values (MWbase) (> 0). Unit = MW.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::qnl | 
No-load flow at nominal head (qnl) (>=0). Typical Value = 0.08.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::rperm | 
Permanent droop (R) (>0). Typical Value = 0.04.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::rtemp | 
Temporary droop (r) (>R). Typical Value = 0.3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tf | 
Filter time constant (Tf) (>0). Typical Value = 0.05.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tg | 
Gate servo time constant (Tg) (>0). Typical Value = 0.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tr | 
Washout time constant (Tr) (>0). Typical Value = 5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tw | 
Water inertia time constant (Tw) (>0). Typical Value = 1.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::velm | 
Maximum gate velocity (Vlem) (>0). Typical Value = 0.2.
 1.8.13
 1.8.13