#include <GovGASTWD.h>


Woodward Gas turbine governor model.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::a | 
Valve positioner (A).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::af1 | 
Exhaust temperature Parameter (Af1).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::af2 | 
Coefficient equal to 0.5(1-speed) (Af2).
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::b | 
Valve positioner (B).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::bf1 | 
(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0.55 to 0.65 x Tr.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::bf2 | 
Turbine Torque Coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2).
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::c | 
Valve positioner (C).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::cf2 | 
Coefficient defining fuel flow where power output is 0% (Cf2). Synchronous but no output. Typically 0.23 x Khhv (23% fuel flow).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::ecr | 
Combustion reaction time delay (Ecr).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::etd | 
Turbine and exhaust delay (Etd).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k3 | 
Ratio of Fuel Adjustment (K3).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k4 | 
Gain of radiation shield (K4).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k5 | 
Gain of radiation shield (K5).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k6 | 
Minimum fuel flow (K6).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kd | 
Drop Governor Gain (Kd).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kdroop | 
(Kdroop).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kf | 
Fuel system feedback (Kf).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::ki | 
Isochronous Governor Gain (Ki).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kp | 
PID Proportional gain (Kp).
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::mwbase | 
Base for power values (MWbase) (> 0). Unit = MW.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t | 
Fuel Control Time Constant (T).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t3 | 
Radiation shield time constant (T3).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t4 | 
Thermocouple time constant (T4).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t5 | 
Temperature control time constant (T5).
| IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tc | 
Temperature control (Tc).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tcd | 
Compressor discharge time constant (Tcd).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::td | 
Power transducer time constant (Td).
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tf | 
Fuel system time constant (Tf).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tmax | 
Maximum Turbine limit (Tmax).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tmin | 
Minimum Turbine limit (Tmin).
| IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tr | 
Rated temperature (Tr).
| IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::trate | 
Turbine rating (Trate). Unit = MW.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tt | 
Temperature controller integration rate (Tt).
 1.8.13