#include <GovGAST3.h>


Generic turbogas with acceleration and temperature controller.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::bca | 
Acceleration limit set-point (Bca). Unit = 1/s. Typical Value = 0.01.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::bp | 
Droop (bp). Typical Value = 0.05.
| IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::dtc | 
Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical Value = 390.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ka | 
Minimum fuel flow (Ka). Typical Value = 0.23.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::kac | 
Fuel system feedback (KAC). Typical Value = 0.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::kca | 
Acceleration control integral gain (Kca). Unit = 1/s. Typical Value = 100.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ksi | 
Gain of radiation shield (Ksi). Typical Value = 0.8.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ky | 
Coefficient of transfer function of fuel valve positioner (Ky). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::mnef | 
Fuel flow maximum negative error value (MNEF). Typical Value = -0. 05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::mxef | 
Fuel flow maximum positive error value (MXEF). Typical Value = 0.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::rcmn | 
Minimum fuel flow (RCMN). Typical Value = -0.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::rcmx | 
Maximum fuel flow (RCMX). Typical Value = 1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tac | 
Fuel control time constant (Tac). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tc | 
Compressor discharge volume time constant (Tc). Typical Value = 0.2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::td | 
Temperature controller derivative gain (Td). Typical Value = 3.3.
| IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tfen | 
Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical Value = 540.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tg | 
Time constant of speed governor (Tg). Typical Value = 0.05.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tsi | 
Time constant of radiation shield (Tsi). Typical Value = 15.
| IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tt | 
Temperature controller integration rate (Tt). Typical Value = 250.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ttc | 
Time constant of thermocouple (Ttc). Typical Value = 2.5.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ty | 
Time constant of fuel valve positioner (Ty). Typical Value = 0.2.
 1.8.13
 1.8.13