#include <PssSK.h>


PSS Slovakian type – three inputs.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::k1 | 
Gain P (K1). Typical Value = -0.3.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::k2 | 
Gain fe (K2). Typical Value = -0.15.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::k3 | 
Gain If (K3). Typical Value = 10.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t1 | 
Denominator time constant (T1). Typical Value = 0.3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t2 | 
Filter time constant (T2). Typical Value = 0.35.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t3 | 
Denominator time constant (T3). Typical Value = 0.22.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t4 | 
Filter time constant (T4). Typical Value = 0.02.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t5 | 
Denominator time constant (T5). Typical Value = 0.02.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t6 | 
Filter time constant (T6). Typical Value = 0.02.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::vsmax | 
Stabilizer output max limit (Vsmax). Typical Value = 0.4.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::vsmin | 
Stabilizer output min limit (Vsmin). Typical Value = -0.4.