Public Attributes

IEC61970::Base::Domain::PU a0
 
IEC61970::Base::Domain::PU a1
 
IEC61970::Base::Domain::PU a2
 
IEC61970::Base::Domain::PU a3
 
IEC61970::Base::Domain::PU a4
 
IEC61970::Base::Domain::PU a5
 
IEC61970::Base::Domain::PU al
 
IEC61970::Base::Domain::PU athres
 
IEC61970::Base::Domain::PU b0
 
IEC61970::Base::Domain::PU b1
 
IEC61970::Base::Domain::PU b2
 
IEC61970::Base::Domain::PU b3
 
IEC61970::Base::Domain::PU b4
 
IEC61970::Base::Domain::PU b5
 
IEC61970::Base::Domain::PU dl
 
IEC61970::Base::Domain::Seconds dtc
 
IEC61970::Base::Domain::Seconds dtf
 
IEC61970::Base::Domain::Seconds dtp
 
IEC61970::Base::Domain::Boolean isw
 
IEC61970::Base::Domain::PU k
 
IEC61970::Base::Domain::PU lthres
 
IEC61970::Base::Domain::PU m
 
IEC61970::Base::Domain::Float nav
 
IEC61970::Base::Domain::Float ncl
 
IEC61970::Base::Domain::Float ncr
 
IEC61970::Base::Domain::PU pmin
 
IEC61970::Base::Domain::Seconds t1
 
IEC61970::Base::Domain::Seconds t2
 
IEC61970::Base::Domain::Seconds t3
 
IEC61970::Base::Domain::Seconds t4
 
IEC61970::Base::Domain::Seconds t5
 
IEC61970::Base::Domain::Seconds t6
 
IEC61970::Base::Domain::Seconds tf
 
IEC61970::Base::Domain::Seconds tp
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PowerSystemStabilizerDynamics
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamicsExcitationSystemDynamics
 
std::list< IEC61970::Dynamics::StandardInterconnections::RemoteInputSignal * > RemoteInputSignal
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

PTI Microprocessor-Based Stabilizer type 3.

Member Data Documentation

◆ a0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::a0

Filter coefficient (A0).

◆ a1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::a1

Limiter (Al).

◆ a2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::a2

Filter coefficient (A2).

◆ a3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::a3

Filter coefficient (A3).

◆ a4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::a4

Filter coefficient (A4).

◆ a5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::a5

Filter coefficient (A5).

◆ al

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::al

Limiter (Al).

◆ athres

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::athres

Threshold value above which output averaging will be bypassed (Athres). Typical Value = 0.005.

◆ b0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::b0

Filter coefficient (B0).

◆ b1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::b1

Filter coefficient (B1).

◆ b2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::b2

Filter coefficient (B2).

◆ b3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::b3

Filter coefficient (B3).

◆ b4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::b4

Filter coefficient (B4).

◆ b5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::b5

Filter coefficient (B5).

◆ dl

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::dl

Limiter (Dl).

◆ dtc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::dtc

Time step related to activation of controls (0.03 for 50 Hz) (Dtc). Typical Value = 0.025.

◆ dtf

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::dtf

Time step frequency calculation (0.03 for 50 Hz) (Dtf). Typical Value = 0.025.

◆ dtp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::dtp

Time step active power calculation (0.015 for 50 Hz) (Dtp). Typical Value = 0. 0125.

◆ isw

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::isw

Digital/analog output switch (Isw). true = produce analog output false = convert to digital output, using tap selection table.

◆ k

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::k

Gain (K). Typical Value = 9.

◆ lthres

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::lthres

Threshold value (Lthres).

◆ m

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::m

(M). M=2*H. Typical Value = 5.

◆ nav

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::nav

Number of control outputs to average (Nav) (1 <= Nav <= 16). Typical Value = 4.

◆ ncl

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::ncl

Number of counts at limit to active limit function (Ncl) (>0).

◆ ncr

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::ncr

Number of counts until reset after limit function is triggered (Ncr).

◆ pmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::pmin

(Pmin).

◆ t1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::t1

Time constant (T1). Typical Value = 0.3.

◆ t2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::t2

Time constant (T2). Typical Value = 1.

◆ t3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::t3

Time constant (T3). Typical Value = 0.2.

◆ t4

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::t4

Time constant (T4). Typical Value = 0.05.

◆ t5

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::t5

Time constant (T5).

◆ t6

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::t6

Time constant (T6).

◆ tf

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::tf

Time constant (Tf). Typical Value = 0.2.

◆ tp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssPTIST3::tp

Time constant (Tp). Typical Value = 0.2.