#include <PssIEEE2B.h>


The class represents IEEE Std 421.5-2005 type PSS2B power system stabilizer model. This stabilizer model is designed to represent a variety of dual-input stabilizers, which normally use combinations of power and speed or frequency to derive the stabilizing signal.
Reference: IEEE 2B 421.5-2005 Section 8.2.
| IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::inputSignal1Type = IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind::_undef | 
Type of input signal #1. Typical Value = rotorSpeed.
| IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::inputSignal2Type = IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind::_undef | 
Type of input signal #2. Typical Value = generatorElectricalPower.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::ks1 | 
Stabilizer gain (Ks1). Typical Value = 12.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::ks2 | 
Gain on signal #2 (Ks2). Typical Value = 0.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::ks3 | 
Gain on signal #2 input before ramp-tracking filter (Ks3). Typical Value = 1.
| IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::m | 
Denominator order of ramp tracking filter (M). Typical Value = 5.
| IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::n | 
Order of ramp tracking filter (N). Typical Value = 1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t1 | 
Lead/lag time constant (T1). Typical Value = 0.12.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t10 | 
Lead/lag time constant (T10). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t11 | 
Lead/lag time constant (T11). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t2 | 
Lead/lag time constant (T2). Typical Value = 0.02.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t3 | 
Lead/lag time constant (T3). Typical Value = 0.3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t4 | 
Lead/lag time constant (T4). Typical Value = 0.02.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t6 | 
Time constant on signal #1 (T6). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t7 | 
Time constant on signal #2 (T7). Typical Value = 2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t8 | 
Lead of ramp tracking filter (T8). Typical Value = 0.2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::t9 | 
Lag of ramp tracking filter (T9). Typical Value = 0.1.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::tw1 | 
First washout on signal #1 (Tw1). Typical Value = 2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::tw2 | 
Second washout on signal #1 (Tw2). Typical Value = 2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::tw3 | 
First washout on signal #2 (Tw3). Typical Value = 2.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::tw4 | 
Second washout on signal #2 (Tw4). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::vsi1max | 
Input signal #1 max limit (Vsi1max). Typical Value = 2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::vsi1min | 
Input signal #1 min limit (Vsi1min). Typical Value = -2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::vsi2max | 
Input signal #2 max limit (Vsi2max). Typical Value = 2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::vsi2min | 
Input signal #2 min limit (Vsi2min). Typical Value = -2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::vstmax | 
Stabilizer output max limit (Vstmax). Typical Value = 0.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssIEEE2B::vstmin | 
Stabilizer output min limit (Vstmin). Typical Value = -0.1.
 1.8.13