#include <OverexcLimX2.h>


Field Voltage or Current overexcitation limiter designed to protect the generator field of an AC machine with automatic excitation control from overheating due to prolonged overexcitation.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efd1 | 
Low voltage or current point on the inverse time characteristic (EFD1). Typical Value = 1.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efd2 | 
Mid voltage or current point on the inverse time characteristic (EFD2). Typical Value = 1.2.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efd3 | 
High voltage or current point on the inverse time characteristic (EFD3). Typical Value = 1.5.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efddes | 
Desired field voltage if m=F or field current if m=T (EFDDES). Typical Value = 1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efdrated | 
Rated field voltage if m=F or field current if m=T (EFDRATED). Typical Value = 1.05.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::kmx | 
Gain (KMX). Typical Value = 0.002.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::m | 
(m). true = IFD limiting false = EFD limiting.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::t1 | 
Time to trip the exciter at the low voltage or current point on the inverse time characteristic (TIME1). Typical Value = 120.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::t2 | 
Time to trip the exciter at the mid voltage or current point on the inverse time characteristic (TIME2). Typical Value = 40.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::t3 | 
Time to trip the exciter at the high voltage or current point on the inverse time characteristic (TIME3). Typical Value = 15.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::vlow | 
Low voltage limit (VLOW) (>0).
 1.8.13