IEC61970 17v23
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A Class Reference

#include <ExcST2A.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU efdmax
 
IEC61970::Base::Domain::PU ka
 
IEC61970::Base::Domain::PU kc
 
IEC61970::Base::Domain::PU ke
 
IEC61970::Base::Domain::PU kf
 
IEC61970::Base::Domain::PU ki
 
IEC61970::Base::Domain::PU kp
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tb
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::Seconds te
 
IEC61970::Base::Domain::Seconds tf
 
IEC61970::Base::Domain::Boolean uelin
 
IEC61970::Base::Domain::PU vrmax
 
IEC61970::Base::Domain::PU vrmin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Modified IEEE ST2A static excitation system - another lead-lag block added to match the model defined by WECC.

Member Data Documentation

◆ efdmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::efdmax

Maximum field voltage (Efdmax). Typical Value = 99.

◆ ka

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::ka

Voltage regulator gain (Ka). Typical Value = 120.

◆ kc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::kc

Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 1.82.

◆ ke

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::ke

Exciter constant related to self-excited field (Ke). Typical Value = 1.

◆ kf

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::kf

Excitation control system stabilizer gains (Kf). Typical Value = 0.05.

◆ ki

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::ki

Potential circuit gain coefficient (Ki). Typical Value = 8.

◆ kp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::kp

Potential circuit gain coefficient (Kp). Typical Value = 4.88.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::ta

Voltage regulator time constant (Ta). Typical Value = 0.15.

◆ tb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::tb

Voltage regulator time constant (Tb). Typical Value = 0.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::tc

Voltage regulator time constant (Tc). Typical Value = 0.

◆ te

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::te

Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 0.5.

◆ tf

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::tf

Excitation control system stabilizer time constant (Tf). Typical Value = 0.7.

◆ uelin

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::uelin

UEL input (UELin). true = HV gate false = add to error signal. Typical Value = false.

◆ vrmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::vrmax

Maximum voltage regulator outputs (Vrmax). Typical Value = 1.

◆ vrmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST2A::vrmin

Minimum voltage regulator outputs (Vrmin). Typical Value = -1.