IEC61970::Base::Domain::PU efd1
 
IEC61970::Base::Domain::PU efd2
 
IEC61970::Base::Domain::Boolean exclim
 
IEC61970::Base::Domain::PU ke
 
IEC61970::Base::Domain::PU kv
 
IEC61970::Base::Domain::Float seefd1
 
IEC61970::Base::Domain::Float seefd2
 
IEC61970::Base::Domain::Seconds te
 
IEC61970::Base::Domain::Seconds trh
 
IEC61970::Base::Domain::PU vrmax
 
IEC61970::Base::Domain::PU vrmin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

The class represents IEEE Std 421.5-2005 type DC3A model. This model represents represent older systems, in particular those dc commutator exciters with non- continuously acting regulators that were commonly used before the development of the continuously acting varieties. These systems respond at basically two different rates, depending upon the magnitude of voltage error. For small errors, adjustment is made periodically with a signal to a motor-operated rheostat. Larger errors cause resistors to be quickly shorted or inserted and a strong forcing signal applied to the exciter. Continuous motion of the motor- operated rheostat occurs for these larger error signals, even though it is bypassed by contactor action.

Reference: IEEE Standard 421.5-2005 Section 5.3.

Member Data Documentation

◆ efd1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::efd1

Exciter voltage at which exciter saturation is defined (EFD1). Typical Value = 3.375.

◆ efd2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::efd2

Exciter voltage at which exciter saturation is defined (EFD2). Typical Value = 3.15.

◆ exclim

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::exclim

(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero is not applied to integrator output. Typical Value = true.

◆ ke

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::ke

Exciter constant related to self-excited field (KE). Typical Value = 0.05.

◆ kv

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::kv

Fast raise/lower contact setting (KV). Typical Value = 0.05.

◆ seefd1

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::seefd1

Exciter saturation function value at the corresponding exciter voltage, EFD1 (SE[EFD1]). Typical Value = 0.267.

◆ seefd2

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::seefd2

Exciter saturation function value at the corresponding exciter voltage, EFD2 (SE[EFD2]). Typical Value = 0.068.

◆ te

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::te

Exciter time constant, integration rate associated with exciter control (TE). Typical Value = 0.5.

◆ trh

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::trh

Rheostat travel time (TRH). Typical Value = 20.

◆ vrmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::vrmax

Maximum voltage regulator output (VRMAX). Typical Value = 1.

◆ vrmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEDC3A::vrmin

Minimum voltage regulator output (VRMIN). Typical Value = 0.