IEC61970 17v23
Public Attributes | List of all members
IEC61970::Base::Wires::PowerElectronicsConnection Class Reference

#include <PowerElectronicsConnection.h>

Inheritance diagram for IEC61970::Base::Wires::PowerElectronicsConnection:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Base::Wires::PowerElectronicsConnection:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::ReactivePower maxQ
 
IEC61970::Base::Domain::ReactivePower minQ
 
IEC61970::Base::Domain::ActivePower p
 
IEC61970::Base::Domain::ReactivePower q
 
IEC61970::Base::Domain::Resistance r
 
IEC61970::Base::Domain::Resistance r0
 
IEC61970::Base::Domain::ApparentPower ratedS
 
IEC61970::Base::Domain::Voltage ratedU
 
IEC61970::Base::Domain::Resistance rn
 
IEC61970::Base::Domain::Reactance x
 
IEC61970::Base::Domain::Reactance x0
 
IEC61970::Base::Domain::Reactance xn
 
std::list< IEC61970::Base::Generation::Production::PowerElectronicsUnit * > PowerElectronicsUnit
 
- Public Attributes inherited from IEC61970::Base::Wires::RegulatingCondEq
IEC61970::Base::Domain::Boolean controlEnabled
 
IEC61970::Base::Wires::RegulatingControlRegulatingControl
 
- Public Attributes inherited from IEC61970::Base::Core::Equipment
IEC61970::Base::Domain::Boolean aggregate
 
IEC61970::Base::Domain::Boolean inService
 
IEC61970::Base::Domain::Boolean networkAnalysisEnabled
 
IEC61970::Base::Domain::Boolean normallyInService
 
- Public Attributes inherited from IEC61970::Base::Core::PowerSystemResource
std::list< IEC61970::Base::Meas::Control * > Controls
 
std::list< IEC61970::Base::Meas::Measurement * > Measurements
 
IEC61970::Base::Core::PSRTypePSRType
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

A connection to the AC network for energy production or consumption that uses power electronics rather than rotating machines.

Member Data Documentation

◆ maxQ

IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::PowerElectronicsConnection::maxQ

Maximum reactive power limit. This is the maximum (nameplate) limit for the unit.

◆ minQ

IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::PowerElectronicsConnection::minQ

Minimum reactive power limit for the unit. This is the minimum (nameplate) limit for the unit.

◆ p

IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::PowerElectronicsConnection::p

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution.

◆ q

IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::PowerElectronicsConnection::q

Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for a steady state solution.

◆ r

IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::PowerElectronicsConnection::r

Equivalent resistance (RG) of generator. RG is considered for the calculation of all currents, except for the calculation of the peak current ip. Used for short circuit data exchange according to IEC 60909.

◆ r0

IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::PowerElectronicsConnection::r0

Zero sequence resistance of the synchronous machine.

◆ ratedS

IEC61970::Base::Domain::ApparentPower IEC61970::Base::Wires::PowerElectronicsConnection::ratedS

Nameplate apparent power rating for the unit. The attribute shall have a positive value.

◆ ratedU

IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::PowerElectronicsConnection::ratedU

Rated voltage (nameplate data, Ur in IEC 60909-0). It is primarily used for short circuit data exchange according to IEC 60909.

◆ rn

IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::PowerElectronicsConnection::rn

Negative sequence Thevenin resistance.

◆ x

IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::PowerElectronicsConnection::x

Positive sequence Thevenin reactance.

◆ x0

IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::PowerElectronicsConnection::x0

Zero sequence Thevenin reactance.

◆ xn

IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::PowerElectronicsConnection::xn

Negative sequence Thevenin reactance.