#include <VsConverter.h>
DC side of the voltage source converter (VSC).
IEC61970::Base::DC::VsCapabilityCurve* IEC61970::Base::DC::VsConverter::CapabilityCurve |
Capability curve of this converter.
IEC61970::Base::Domain::AngleDegrees IEC61970::Base::DC::VsConverter::delta |
Angle between uf and uc. Converter state variable used in power flow.
IEC61970::Base::Domain::PU IEC61970::Base::DC::VsConverter::droop |
Droop constant; pu value is obtained as D [kV/MW] x Sb / Ubdc.
IEC61970::Base::Domain::Resistance IEC61970::Base::DC::VsConverter::droopCompensation |
Compensation constant. Used to compensate for voltage drop when controlling voltage at a distant bus.
IEC61970::Base::Domain::Float IEC61970::Base::DC::VsConverter::maxModulationIndex |
The max quotient between the AC converter voltage (Uc) and DC voltage (Ud). A factor typically less than 1. VSC configuration data used in power flow.
IEC61970::Base::Domain::CurrentFlow IEC61970::Base::DC::VsConverter::maxValveCurrent |
The maximum current through a valve. This current limit is the basis for calculating the capability diagram. VSC configuration data.
IEC61970::Base::DC::VsPpccControlKind IEC61970::Base::DC::VsConverter::pPccControl = IEC61970::Base::DC::VsPpccControlKind::_undef |
Kind of control of real power and/or DC voltage.
IEC61970::Base::Domain::PerCent IEC61970::Base::DC::VsConverter::qShare |
Reactive power sharing factor among parallel converters on Uac control.
IEC61970::Base::Domain::ReactivePower IEC61970::Base::DC::VsConverter::targetQpcc |
Reactive power injection target in AC grid, at point of common coupling.
IEC61970::Base::Domain::Voltage IEC61970::Base::DC::VsConverter::targetUpcc |
Voltage target in AC grid, at point of common coupling.
IEC61970::Base::Domain::Voltage IEC61970::Base::DC::VsConverter::uv |
Line-to-line voltage on the valve side of the converter transformer. Converter state variable, result from power flow.