IEC61970 17v07
Public Attributes | List of all members
IEC61970::Base::Wires::TapChangerControl Class Reference

#include <TapChangerControl.h>

Inheritance diagram for IEC61970::Base::Wires::TapChangerControl:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Base::Wires::TapChangerControl:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::Voltage limitVoltage
 
IEC61970::Base::Domain::Boolean lineDropCompensation
 
IEC61970::Base::Domain::Resistance lineDropR
 
IEC61970::Base::Domain::Reactance lineDropX
 
IEC61970::Base::Domain::Resistance reverseLineDropR
 
IEC61970::Base::Domain::Reactance reverseLineDropX
 
- Public Attributes inherited from IEC61970::Base::Wires::RegulatingControl
IEC61970::Base::Domain::Boolean discrete
 
IEC61970::Base::Domain::Boolean enabled
 
IEC61970::Base::Wires::RegulatingControlModeKind mode = IEC61970::Base::Wires::RegulatingControlModeKind::_undef
 
IEC61970::Base::Core::PhaseCode monitoredPhase = IEC61970::Base::Core::PhaseCode::_undef
 
IEC61970::Base::Domain::Float targetDeadband
 
IEC61970::Base::Domain::Float targetValue
 
IEC61970::Base::Domain::UnitMultiplier targetValueUnitMultiplier = IEC61970::Base::Domain::UnitMultiplier::_undef
 
- Public Attributes inherited from IEC61970::Base::Core::PowerSystemResource
std::list< IEC61970::Base::Meas::Control * > Controls
 
std::list< IEC61970::Base::Meas::Measurement * > Measurements
 
IEC61970::Base::Core::PSRTypePSRType
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Describes behavior specific to tap changers, e.g. how the voltage at the end of a line varies with the load level and compensation of the voltage drop by tap adjustment.

Member Data Documentation

◆ limitVoltage

IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::TapChangerControl::limitVoltage

Maximum allowed regulated voltage on the PT secondary, regardless of line drop compensation. Sometimes referred to as first-house protection.

◆ lineDropCompensation

IEC61970::Base::Domain::Boolean IEC61970::Base::Wires::TapChangerControl::lineDropCompensation

If true, the line drop compensation is to be applied.

◆ lineDropR

IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::TapChangerControl::lineDropR

Line drop compensator resistance setting for normal (forward) power flow.

◆ lineDropX

IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::TapChangerControl::lineDropX

Line drop compensator reactance setting for normal (forward) power flow.

◆ reverseLineDropR

IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::TapChangerControl::reverseLineDropR

Line drop compensator resistance setting for reverse power flow.

◆ reverseLineDropX

IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::TapChangerControl::reverseLineDropX

Line drop compensator reactance setting for reverse power flow.


The documentation for this class was generated from the following files: