#include <TapChangerControl.h>
Describes behavior specific to tap changers, e.g. how the voltage at the end of a line varies with the load level and compensation of the voltage drop by tap adjustment.
IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::TapChangerControl::limitVoltage |
Maximum allowed regulated voltage on the PT secondary, regardless of line drop compensation. Sometimes referred to as first-house protection.
IEC61970::Base::Domain::Boolean IEC61970::Base::Wires::TapChangerControl::lineDropCompensation |
If true, the line drop compensation is to be applied.
IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::TapChangerControl::lineDropR |
Line drop compensator resistance setting for normal (forward) power flow.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::TapChangerControl::lineDropX |
Line drop compensator reactance setting for normal (forward) power flow.
IEC61970::Base::Domain::Resistance IEC61970::Base::Wires::TapChangerControl::reverseLineDropR |
Line drop compensator resistance setting for reverse power flow.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::TapChangerControl::reverseLineDropX |
Line drop compensator reactance setting for reverse power flow.