#include <PetersenCoil.h>
A tunable impedance device normally used to offset line charging during single line faults in an ungrounded section of network.
IEC61970::Base::Wires::PetersenCoilModeKind IEC61970::Base::Wires::PetersenCoil::mode = IEC61970::Base::Wires::PetersenCoilModeKind::_undef |
The mode of operation of the Petersen coil.
IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::PetersenCoil::nominalU |
The nominal voltage for which the coil is designed.
IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::PetersenCoil::offsetCurrent |
The offset current that the Petersen coil controller is operating from the resonant point. This is normally a fixed amount for which the controller is configured and could be positive or negative. Typically 0 to 60 Amperes depending on voltage and resonance conditions.
IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::PetersenCoil::positionCurrent |
The control current used to control the Petersen coil also known as the position current. Typically in the range of 20-200mA.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::PetersenCoil::xGroundMax |
The maximum reactance.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::PetersenCoil::xGroundMin |
The minimum reactance.
IEC61970::Base::Domain::Reactance IEC61970::Base::Wires::PetersenCoil::xGroundNominal |
The nominal reactance. This is the operating point (normally over compensation) that is defined based on the resonance point in the healthy network condition. The impedance is calculated based on nominal voltage divided by position current.