IEC61970 17v07
Public Attributes | List of all members
IEC61970::Base::Equivalents::EquivalentBranch Class Reference

#include <EquivalentBranch.h>

Inheritance diagram for IEC61970::Base::Equivalents::EquivalentBranch:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Base::Equivalents::EquivalentBranch:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::Resistance negativeR12
 
IEC61970::Base::Domain::Resistance negativeR21
 
IEC61970::Base::Domain::Reactance negativeX12
 
IEC61970::Base::Domain::Reactance negativeX21
 
IEC61970::Base::Domain::Resistance positiveR12
 
IEC61970::Base::Domain::Resistance positiveR21
 
IEC61970::Base::Domain::Reactance positiveX12
 
IEC61970::Base::Domain::Reactance positiveX21
 
IEC61970::Base::Domain::Resistance r
 
IEC61970::Base::Domain::Resistance r21
 
IEC61970::Base::Domain::Reactance x
 
IEC61970::Base::Domain::Reactance x21
 
IEC61970::Base::Domain::Resistance zeroR12
 
IEC61970::Base::Domain::Resistance zeroR21
 
IEC61970::Base::Domain::Reactance zeroX12
 
IEC61970::Base::Domain::Reactance zeroX21
 
- Public Attributes inherited from IEC61970::Base::Core::Equipment
IEC61970::Base::Domain::Boolean aggregate
 
IEC61970::Base::Domain::Boolean inService
 
IEC61970::Base::Domain::Boolean normallyInService
 
- Public Attributes inherited from IEC61970::Base::Core::PowerSystemResource
std::list< IEC61970::Base::Meas::Control * > Controls
 
std::list< IEC61970::Base::Meas::Measurement * > Measurements
 
IEC61970::Base::Core::PSRTypePSRType
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

The class represents equivalent branches.

Member Data Documentation

◆ negativeR12

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::negativeR12

Negative sequence series resistance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange

◆ negativeR21

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::negativeR21

Negative sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange

◆ negativeX12

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::negativeX12

Negative sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange

◆ negativeX21

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::negativeX21

Negative sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909. Usage: EquivalentBranch is a result of network reduction prior to the data exchange

◆ positiveR12

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::positiveR12

Positive sequence series resistance from terminal sequence 1 to terminal sequence 2 . Used for short circuit data exchange according to IEC 60909. EquivalentBranch is a result of network reduction prior to the data exchange.

◆ positiveR21

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::positiveR21

Positive sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange

◆ positiveX12

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::positiveX12

Positive sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange

◆ positiveX21

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::positiveX21

Positive sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange

◆ r

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::r

Positive sequence series resistance of the reduced branch.

◆ r21

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::r21

Resistance from terminal sequence 2 to terminal sequence 1 .Used for steady state power flow. This attribute is optional and represent unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.r is given, then EquivalentBranch.r21 is assumed equal to EquivalentBranch.r. Usage rule : EquivalentBranch is a result of network reduction prior to the data exchange.

◆ x

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::x

Positive sequence series reactance of the reduced branch.

◆ x21

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::x21

Reactance from terminal sequence 2 to terminal sequence 1 .Used for steady state power flow. This attribute is optional and represent unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.x is given, then EquivalentBranch.x21 is assumed equal to EquivalentBranch.x. Usage rule : EquivalentBranch is a result of network reduction prior to the data exchange.

◆ zeroR12

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::zeroR12

Zero sequence series resistance from terminal sequence 1 to terminal sequence

  1. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange

◆ zeroR21

IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::zeroR21

Zero sequence series resistance from terminal sequence 2 to terminal sequence

  1. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange

◆ zeroX12

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::zeroX12

Zero sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange

◆ zeroX21

IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::zeroX21

Zero sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange


The documentation for this class was generated from the following files: