CIM++ Adapted CIM_SINERGIEN Codebase
|
#include <ShuntCompensator.h>
A shunt capacitor or reactor or switchable bank of shunt capacitors or reactors. A section of a shunt compensator is an individual capacitor or reactor. A negative value for reactivePerSection indicates that the compensator is a reactor. ShuntCompensator is a single terminal device. Ground is implied.
IEC61970::Base::Domain::Seconds IEC61970::Base::Wires::ShuntCompensator::aVRDelay |
Time delay required for the device to be connected or disconnected by automatic voltage regulation (AVR).
IEC61970::Base::Domain::Boolean IEC61970::Base::Wires::ShuntCompensator::grounded |
Used for Yn and Zn connections. True if the neutral is solidly grounded.
IEC61970::Base::Domain::Integer IEC61970::Base::Wires::ShuntCompensator::maximumSections |
The maximum number of sections that may be switched in.
IEC61970::Base::Domain::Voltage IEC61970::Base::Wires::ShuntCompensator::nomU |
The voltage at which the nominal reactive power may be calculated. This should normally be within 10% of the voltage at which the capacitor is connected to the network.
IEC61970::Base::Domain::Integer IEC61970::Base::Wires::ShuntCompensator::normalSections |
The normal number of sections switched in.
IEC61970::Base::Wires::PhaseShuntConnectionKind IEC61970::Base::Wires::ShuntCompensator::phaseConnection |
The type of phase connection, such as wye or delta.
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ShuntCompensator::sections |
Shunt compensator sections in use. Starting value for steady state solution. Non integer values are allowed to support continuous variables. The reasons for continuous value are to support study cases where no discrete shunt compensators has yet been designed, a solutions where a narrow voltage band force the sections to oscillate or accommodate for a continuous solution as input.
std::list<IEC61970::Base::Wires::ShuntCompensatorPhase*> IEC61970::Base::Wires::ShuntCompensator::ShuntCompensatorPhase |
The individual phases models for the shunt compensator.
IEC61970::Base::Domain::Integer IEC61970::Base::Wires::ShuntCompensator::switchOnCount |
The switch on count since the capacitor count was last reset or initialized.
IEC61970::Base::Domain::DateTime IEC61970::Base::Wires::ShuntCompensator::switchOnDate |
The date and time when the capacitor bank was last switched on.
IEC61970::Base::Domain::VoltagePerReactivePower IEC61970::Base::Wires::ShuntCompensator::voltageSensitivity |
Voltage sensitivity required for the device to regulate the bus voltage, in voltage/reactive power.