The class represents equivalent branches.
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::negativeR12 |
Negative sequence series resistance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::negativeR21 |
Negative sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::negativeX12 |
Negative sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::negativeX21 |
Negative sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909. Usage: EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::positiveR12 |
Positive sequence series resistance from terminal sequence 1 to terminal sequence 2 . Used for short circuit data exchange according to IEC 60909. EquivalentBranch is a result of network reduction prior to the data exchange.
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::positiveR21 |
Positive sequence series resistance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::positiveX12 |
Positive sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::positiveX21 |
Positive sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::r |
Positive sequence series resistance of the reduced branch.
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::r21 |
Resistance from terminal sequence 2 to terminal sequence 1 .Used for steady state power flow. This attribute is optional and represent unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.r is given, then EquivalentBranch.r21 is assumed equal to EquivalentBranch.r. Usage rule : EquivalentBranch is a result of network reduction prior to the data exchange.
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::x |
Positive sequence series reactance of the reduced branch.
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::x21 |
Reactance from terminal sequence 2 to terminal sequence 1 .Used for steady state power flow. This attribute is optional and represent unbalanced network such as off-nominal phase shifter. If only EquivalentBranch.x is given, then EquivalentBranch.x21 is assumed equal to EquivalentBranch.x. Usage rule : EquivalentBranch is a result of network reduction prior to the data exchange.
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::zeroR12 |
Zero sequence series resistance from terminal sequence 1 to terminal sequence
IEC61970::Base::Domain::Resistance IEC61970::Base::Equivalents::EquivalentBranch::zeroR21 |
Zero sequence series resistance from terminal sequence 2 to terminal sequence
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::zeroX12 |
Zero sequence series reactance from terminal sequence 1 to terminal sequence 2. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange
IEC61970::Base::Domain::Reactance IEC61970::Base::Equivalents::EquivalentBranch::zeroX21 |
Zero sequence series reactance from terminal sequence 2 to terminal sequence 1. Used for short circuit data exchange according to IEC 60909 Usage : EquivalentBranch is a result of network reduction prior to the data exchange