IEC61970 17v23
Public Attributes | List of all members
IEC61970::Base::Wires::TapChangerTablePoint Class Reference
Inheritance diagram for IEC61970::Base::Wires::TapChangerTablePoint:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Base::Wires::TapChangerTablePoint:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PerCent b
 
IEC61970::Base::Domain::PerCent g
 
IEC61970::Base::Domain::PerCent r
 
IEC61970::Base::Domain::Float ratio
 
IEC61970::Base::Domain::Integer step
 
IEC61970::Base::Domain::PerCent x
 

Member Data Documentation

◆ b

IEC61970::Base::Domain::PerCent IEC61970::Base::Wires::TapChangerTablePoint::b

The magnetizing branch susceptance deviation in percent of nominal value. The actual susceptance is calculated as follows: calculated magnetizing susceptance = b(nominal) * (1 + b(from this class)/100). The b(nominal) is defined as the static magnetizing susceptance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.

◆ g

IEC61970::Base::Domain::PerCent IEC61970::Base::Wires::TapChangerTablePoint::g

The magnetizing branch conductance deviation in percent of nominal value. The actual conductance is calculated as follows: calculated magnetizing conductance = g(nominal) * (1 + g(from this class)/100). The g(nominal) is defined as the static magnetizing conductance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.

◆ r

IEC61970::Base::Domain::PerCent IEC61970::Base::Wires::TapChangerTablePoint::r

The resistance deviation in percent of nominal value. The actual reactance is calculated as follows: calculated resistance = r(nominal) * (1 + r(from this class)/100). The r(nominal) is defined as the static resistance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.

◆ ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::TapChangerTablePoint::ratio

The voltage at the tap step divided by rated voltage of the transformer end having the tap changer. Hence this is a value close to one. For example, if the ratio at step 1 is 1.01, and the rated voltage of the transformer end is 110kV, then the voltage obtained by setting the tap changer to step 1 to is 111.1kV.

◆ step

IEC61970::Base::Domain::Integer IEC61970::Base::Wires::TapChangerTablePoint::step

The tap step.

◆ x

IEC61970::Base::Domain::PerCent IEC61970::Base::Wires::TapChangerTablePoint::x

The series reactance deviation in percent of nominal value. The actual reactance is calculated as follows: calculated reactance = x(nominal) * (1 + x(from this class)/100). The x(nominal) is defined as the static series reactance on the associated power transformer end or ends. This model assumes the star impedance (pi model) form.


The documentation for this class was generated from the following files: