#include <WindPlantReactiveControlIEC.h>


| Public Attributes | |
| IEC61970::Base::Domain::Float | kiwpx | 
| IEC61970::Base::Domain::Float | kpwpx | 
| IEC61970::Base::Domain::PU | kwpqu | 
| IEC61970::Base::Domain::Boolean | mwppf | 
| IEC61970::Base::Domain::Boolean | mwpu | 
| IEC61970::Base::Domain::Seconds | twppfilt | 
| IEC61970::Base::Domain::Seconds | twpqfilt | 
| IEC61970::Base::Domain::Seconds | twpufilt | 
| IEC61970::Base::Domain::Seconds | txft | 
| IEC61970::Base::Domain::Seconds | txfv | 
| IEC61970::Base::Domain::PU | uwpqdip | 
| IEC61970::Base::Domain::PU | xrefmax | 
| IEC61970::Base::Domain::PU | xrefmin | 
|  Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject | |
| IEC61970::Base::Domain::String | aliasName | 
| IEC61970::Base::Domain::String | description | 
| IEC61970::Base::Domain::String | mRID | 
| IEC61970::Base::Domain::String | name | 
| std::list< IEC61970::Base::DiagramLayout::DiagramObject * > | DiagramObjects | 
Simplified plant voltage and reactive power control model for use with type 3 and type 4 wind turbine models.
Reference: IEC Standard 61400-27-1 Annex E.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kiwpx | 
Plant Q controller integral gain (KIWPx). It is type dependent parameter.
| IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kpwpx | 
Plant Q controller proportional gain (KPWPx). It is type dependent parameter.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::kwpqu | 
Plant voltage control droop (KWPqu). It is project dependent parameter.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::mwppf | 
Power factor control modes selector (MWPpf). Used only if mwpu is set to false. true = 1: power factor control false = 0: reactive power control. It is project dependent parameter.
| IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::mwpu | 
Reactive power control modes selector (MWPu). true = 1: voltage control false = 0: reactive power control. It is project dependent parameter.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::twppfilt | 
Filter time constant for active power measurement (TWPpfilt). It is type dependent parameter.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::twpqfilt | 
Filter time constant for reactive power measurement (TWPqfilt). It is type dependent parameter.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::twpufilt | 
Filter time constant for voltage measurement (TWPufilt). It is type dependent parameter.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::txft | 
Lead time constant in reference value transfer function (Txft). It is type dependent parameter.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::txfv | 
Lag time constant in reference value transfer function (Txfv). It is type dependent parameter.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::uwpqdip | 
Voltage threshold for LVRT detection in q control (uWPqdip). It is type dependent parameter.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::xrefmax | 
Maximum xWTref (qWTref or delta uWTref) request from the plant controller (xrefmax). It is project dependent parameter.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindPlantReactiveControlIEC::xrefmin | 
Minimum xWTref (qWTref or deltauWTref) request from the plant controller (xrefmin). It is project dependent parameter.