#include <WindContQIEC.h>
Q control model.
Reference: IEC Standard 61400-27-1 Section 6.6.5.6.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::iqh1 |
Maximum reactive current injection during dip (iqh1). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::iqmax |
Maximum reactive current injection (iqmax). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::iqmin |
Minimum reactive current injection (iqmin). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::iqpost |
Post fault reactive current injection (iqpost). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::kiq |
Reactive power PI controller integration gain (KI,q). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::kiu |
Voltage PI controller integration gain (KI,u). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::kpq |
Reactive power PI controller proportional gain (KP,q). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::kpu |
Voltage PI controller proportional gain (KP,u). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::kqv |
Voltage scaling factor for LVRT current (Kqv). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::qmax |
Maximum reactive power (qmax). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::qmin |
Minimum reactive power (qmin). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::rdroop |
Resistive component of voltage drop impedance (rdroop). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::tiq |
Time constant in reactive current lag (Tiq). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::tpfilt |
Power measurement filter time constant (Tpfilt). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::tpost |
Length of time period where post fault reactive power is injected (Tpost). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::tqord |
Time constant in reactive power order lag (Tqord). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::tufilt |
Voltage measurement filter time constant (Tufilt). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::udb1 |
Voltage dead band lower limit (udb1). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::udb2 |
Voltage dead band upper limit (udb2). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::umax |
Maximum voltage in voltage PI controller integral term (umax). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::umin |
Minimum voltage in voltage PI controller integral term (umin). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::uqdip |
Voltage threshold for LVRT detection in q control (uqdip). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::uref0 |
User defined bias in voltage reference (uref0), used when MqG = MG,u. It is case dependent parameter.
IEC61970::Dynamics::StandardModels::WindDynamics::WindLVRTQcontrolModesKind IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::windLVRTQcontrolModesType = IEC61970::Dynamics::StandardModels::WindDynamics::WindLVRTQcontrolModesKind::_undef |
Types of LVRT Q control modes (MqLVRT). It is project dependent parameter.
IEC61970::Dynamics::StandardModels::WindDynamics::WindQcontrolModesKind IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::windQcontrolModesType = IEC61970::Dynamics::StandardModels::WindDynamics::WindQcontrolModesKind::_undef |
Types of general wind turbine Q control modes (MqG). It is project dependent parameter.
IEC61970::Dynamics::StandardModels::WindDynamics::WindTurbineType3or4IEC* IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::WindTurbineType3or4IEC |
Wind turbine type 3 or 4 model with which this reactive control mode is associated.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContQIEC::xdroop |
Inductive component of voltage drop impedance (xdroop). It is project dependent parameter.