#include <TurbLCFB1.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU db
 
IEC61970::Base::Domain::PU emax
 
IEC61970::Base::Domain::PU fb
 
IEC61970::Base::Domain::Boolean fbf
 
IEC61970::Base::Domain::PU irmax
 
IEC61970::Base::Domain::PU ki
 
IEC61970::Base::Domain::PU kp
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::Boolean pbf
 
IEC61970::Base::Domain::ActivePower pmwset
 
IEC61970::Base::Domain::Boolean speedReferenceGovernor
 
IEC61970::Base::Domain::Seconds tpelec
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbineLoadControllerDynamics
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamicsTurbineGovernorDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Turbine Load Controller model developed in the WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.

Member Data Documentation

◆ db

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::db

Controller dead band (db). Typical Value = 0.

◆ emax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::emax

Maximum control error (Emax) (note 4). Typical Value = 0.02.

◆ fb

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::fb

Frequency bias gain (Fb). Typical Value = 0.

◆ fbf

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::fbf

Frequency bias flag (Fbf). true = enable frequency bias false = disable frequency bias. Typical Value = false.

◆ irmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::irmax

Maximum turbine speed/load reference bias (Irmax) (note 3). Typical Value = 0.

◆ ki

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::ki

Integral gain (Ki). Typical Value = 0.

◆ kp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::kp

Proportional gain (Kp). Typical Value = 0.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::mwbase

Base for power values (MWbase) (>0). Unit = MW.

◆ pbf

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::pbf

Power controller flag (Pbf). true = enable load controller false = disable load controller. Typical Value = false.

◆ pmwset

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::pmwset

Power controller setpoint (Pmwset) (note 1). Unit = MW. Typical Value = 0.

◆ speedReferenceGovernor

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::speedReferenceGovernor

Type of turbine governor reference (Type). true = speed reference governor false = load reference governor. Typical Value = true.

◆ tpelec

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::tpelec

Power transducer time constant (Tpelec). Typical Value = 0.


The documentation for this class was generated from the following files: