#include <TurbLCFB1.h>
Turbine Load Controller model developed in the WECC. This model represents a supervisory turbine load controller that acts to maintain turbine power at a set value by continuous adjustment of the turbine governor speed-load reference. This model is intended to represent slow reset 'outer loop' controllers managing the action of the turbine governor.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::db |
Controller dead band (db). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::emax |
Maximum control error (Emax) (note 4). Typical Value = 0.02.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::fb |
Frequency bias gain (Fb). Typical Value = 0.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::fbf |
Frequency bias flag (Fbf). true = enable frequency bias false = disable frequency bias. Typical Value = false.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::irmax |
Maximum turbine speed/load reference bias (Irmax) (note 3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::ki |
Integral gain (Ki). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::kp |
Proportional gain (Kp). Typical Value = 0.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::mwbase |
Base for power values (MWbase) (>0). Unit = MW.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::pbf |
Power controller flag (Pbf). true = enable load controller false = disable load controller. Typical Value = false.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::pmwset |
Power controller setpoint (Pmwset) (note 1). Unit = MW. Typical Value = 0.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::speedReferenceGovernor |
Type of turbine governor reference (Type). true = speed reference governor false = load reference governor. Typical Value = true.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineLoadControllerDynamics::TurbLCFB1::tpelec |
Power transducer time constant (Tpelec). Typical Value = 0.