#include <GovSteamIEEE1.h>
IEEE steam turbine governor model.
Ref<font color="#0f0f0f">erence: IEEE Transactions on Power Apparatus and Systems</font> <font color="#0f0f0f">November/December 1973, Volume PAS-92, Number 6</font> <font color="#0f0f0f"><u>Dynamic Models for Steam and Hydro Turbines in Power System Studies</u>, Page 1904.</font>
Parameter Notes:
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k |
Governor gain (reciprocal of droop) (K) (> 0). Typical Value = 25.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k1 |
Fraction of HP shaft power after first boiler pass (K1). Typical Value = 0.2.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k2 |
Fraction of LP shaft power after first boiler pass (K2). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k3 |
Fraction of HP shaft power after second boiler pass (K3). Typical Value = 0.3.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k4 |
Fraction of LP shaft power after second boiler pass (K4). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k5 |
Fraction of HP shaft power after third boiler pass (K5). Typical Value = 0.5.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k6 |
Fraction of LP shaft power after third boiler pass (K6). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k7 |
Fraction of HP shaft power after fourth boiler pass (K7). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::k8 |
Fraction of LP shaft power after fourth boiler pass (K8). Typical Value = 0.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::mwbase |
Base for power values (MWbase) (> 0).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::pmax |
Maximum valve opening (Pmax) (> Pmin). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::pmin |
Minimum valve opening (Pmin) (>= 0). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t1 |
Governor lag time constant (T1). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t2 |
Governor lead time constant (T2). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t3 |
Valve positioner time constant (T3) (> 0). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t4 |
Inlet piping/steam bowl time constant (T4). Typical Value = 0.3.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t5 |
Time constant of second boiler pass (T5). Typical Value = 5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t6 |
Time constant of third boiler pass (T6). Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::t7 |
Time constant of fourth boiler pass (T7). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::uc |
Maximum valve closing velocity (Uc) (< 0). Unit = PU/sec. Typical Value = -10.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamIEEE1::uo |
Maximum valve opening velocity (Uo) (> 0). Unit = PU/sec. Typical Value = 1.