#include <GovSteam2.h>
Public Attributes | |
IEC61970::Base::Domain::PU | dbf |
IEC61970::Base::Domain::Float | k |
IEC61970::Base::Domain::PU | mnef |
IEC61970::Base::Domain::PU | mxef |
IEC61970::Base::Domain::PU | pmax |
IEC61970::Base::Domain::PU | pmin |
IEC61970::Base::Domain::Seconds | t1 |
IEC61970::Base::Domain::Seconds | t2 |
Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics | |
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamics * | AsynchronousMachineDynamics |
Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock | |
IEC61970::Base::Domain::Boolean | enabled |
Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject | |
IEC61970::Base::Domain::String | aliasName |
IEC61970::Base::Domain::String | description |
IEC61970::Base::Domain::String | mRID |
IEC61970::Base::Domain::String | name |
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > | DiagramObjects |
Simplified governor model.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::dbf |
Frequency dead band (DBF). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::k |
Governor gain (reciprocal of droop) (K). Typical Value = 20.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::mnef |
Fuel flow maximum negative error value (MNEF). Typical Value = -1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::mxef |
Fuel flow maximum positive error value (MXEF). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::pmax |
Maximum fuel flow (PMAX). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::pmin |
Minimum fuel flow (PMIN). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::t1 |
Governor lag time constant (T1) (>0). Typical Value = 0.45.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteam2::t2 |
Governor lead time constant (T2) (may be 0). Typical Value = 0.