#include <GovHydroWPID.h>
Woodward PID Hydro Governor.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::d |
Turbine damping factor (D). Unit = delta P / delta speed.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gatmax |
Gate opening Limit Maximum (Gatmax).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gatmin |
Gate opening Limit Minimum (Gatmin).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gv1 |
Gate position 1 (Gv1).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gv2 |
Gate position 2 (Gv2).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gv3 |
Gate position 3 (Gv3).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::kd |
Derivative gain (Kd). Typical Value = 1.11.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::ki |
Reset gain (Ki). Typical Value = 0.36.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::kp |
Proportional gain (Kp). Typical Value = 0.1.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::mwbase |
Base for power values (MWbase) (>0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pgv1 |
Output at Gv1 PU of MWbase (Pgv1).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pgv2 |
Output at Gv2 PU of MWbase (Pgv2).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pgv3 |
Output at Gv3 PU of MWbase (Pgv3).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pmax |
Maximum Power Output (Pmax).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pmin |
Minimum Power Output (Pmin).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::reg |
Permanent drop (Reg).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::ta |
Controller time constant (Ta) (>0). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::tb |
Gate servo time constant (Tb) (>0). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::treg |
Speed detector time constant (Treg).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::tw |
Water inertia time constant (Tw) (>0). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::velmax |
Maximum gate opening velocity (Velmax). Unit = PU/sec. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::velmin |
Maximum gate closing velocity (Velmin). Unit = PU/sec. Typical Value = 0.