IEC61970 17v07
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR Class Reference

#include <GovHydroR.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU at
 
IEC61970::Base::Domain::Frequency db1
 
IEC61970::Base::Domain::ActivePower db2
 
IEC61970::Base::Domain::PU dturb
 
IEC61970::Base::Domain::Frequency eps
 
IEC61970::Base::Domain::PU gmax
 
IEC61970::Base::Domain::PU gmin
 
IEC61970::Base::Domain::PU gv1
 
IEC61970::Base::Domain::PU gv2
 
IEC61970::Base::Domain::PU gv3
 
IEC61970::Base::Domain::PU gv4
 
IEC61970::Base::Domain::PU gv5
 
IEC61970::Base::Domain::PU gv6
 
IEC61970::Base::Domain::PU h0
 
IEC61970::Base::Domain::Boolean inputSignal
 
IEC61970::Base::Domain::PU kg
 
IEC61970::Base::Domain::PU ki
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::PU pgv1
 
IEC61970::Base::Domain::PU pgv2
 
IEC61970::Base::Domain::PU pgv3
 
IEC61970::Base::Domain::PU pgv4
 
IEC61970::Base::Domain::PU pgv5
 
IEC61970::Base::Domain::PU pgv6
 
IEC61970::Base::Domain::PU pmax
 
IEC61970::Base::Domain::PU pmin
 
IEC61970::Base::Domain::PU qnl
 
IEC61970::Base::Domain::PU r
 
IEC61970::Base::Domain::Seconds t1
 
IEC61970::Base::Domain::Seconds t2
 
IEC61970::Base::Domain::Seconds t3
 
IEC61970::Base::Domain::Seconds t4
 
IEC61970::Base::Domain::Seconds t5
 
IEC61970::Base::Domain::Seconds t6
 
IEC61970::Base::Domain::Seconds t7
 
IEC61970::Base::Domain::Seconds t8
 
IEC61970::Base::Domain::Seconds td
 
IEC61970::Base::Domain::Seconds tp
 
IEC61970::Base::Domain::Seconds tt
 
IEC61970::Base::Domain::Seconds tw
 
IEC61970::Base::Domain::Float velcl
 
IEC61970::Base::Domain::Float velop
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Fourth order lead-lag governor and hydro turbine.

Member Data Documentation

◆ at

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::at

Turbine gain (At). Typical Value = 1.2.

◆ db1

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::db1

Intentional dead-band width (db1). Unit = Hz. Typical Value = 0.

◆ db2

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::db2

Unintentional dead-band (db2). Unit = MW. Typical Value = 0.

◆ dturb

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::dturb

Turbine damping factor (Dturb). Typical Value = 0.2.

◆ eps

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::eps

Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.

◆ gmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gmax

Maximum governor output (Gmax). Typical Value = 1.05.

◆ gmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gmin

Minimum governor output (Gmin). Typical Value = -0.05.

◆ gv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv1

Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0.

◆ gv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv2

Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0.

◆ gv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv3

Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0.

◆ gv4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv4

Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0.

◆ gv5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv5

Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0.

◆ gv6

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv6

Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0.

◆ h0

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::h0

Turbine nominal head (H0). Typical Value = 1.

◆ inputSignal

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::inputSignal

Input signal switch (Flag). true = Pe input is used false = feedback is received from CV. Flag is normally dependent on Tt. If Tf is zero, Flag is set to false. If Tf is not zero, Flag is set to true. Typical Value = true.

◆ kg

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::kg

Gate servo gain (Kg). Typical Value = 2.

◆ ki

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::ki

Integral gain (Ki). Typical Value = 0.5.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::mwbase

Base for power values (MWbase) (>0). Unit = MW.

◆ pgv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv1

Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0.

◆ pgv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv2

Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0.

◆ pgv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv3

Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0.

◆ pgv4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv4

Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0.

◆ pgv5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv5

Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0.

◆ pgv6

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv6

Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0.

◆ pmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pmax

Maximum gate opening, PU of MWbase (Pmax). Typical Value = 1.

◆ pmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pmin

Minimum gate opening, PU of MWbase (Pmin). Typical Value = 0.

◆ qnl

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::qnl

No-load turbine flow at nominal head (Qnl). Typical Value = 0.08.

◆ r

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::r

Steady-state droop (R). Typical Value = 0.05.

◆ t1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t1

Lead time constant 1 (T1). Typical Value = 1.5.

◆ t2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t2

Lag time constant 1 (T2). Typical Value = 0.1.

◆ t3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t3

Lead time constant 2 (T3). Typical Value = 1.5.

◆ t4

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t4

Lag time constant 2 (T4). Typical Value = 0.1.

◆ t5

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t5

Lead time constant 3 (T5). Typical Value = 0.

◆ t6

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t6

Lag time constant 3 (T6). Typical Value = 0.05.

◆ t7

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t7

Lead time constant 4 (T7). Typical Value = 0.

◆ t8

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t8

Lag time constant 4 (T8). Typical Value = 0.05.

◆ td

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::td

Input filter time constant (Td). Typical Value = 0.05.

◆ tp

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::tp

Gate servo time constant (Tp). Typical Value = 0.05.

◆ tt

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::tt

Power feedback time constant (Tt). Typical Value = 0.

◆ tw

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::tw

Water inertia time constant (Tw). Typical Value = 1.

◆ velcl

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::velcl

Maximum gate closing velocity (Velcl). Unit = PU/sec. Typical Value = -0.2.

◆ velop

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::velop

Maximum gate opening velocity (Velop). Unit = PU/sec. Typical Value = 0.2.


The documentation for this class was generated from the following files: