#include <GovGAST3.h>
Generic turbogas with acceleration and temperature controller.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::bca |
Acceleration limit set-point (Bca). Unit = 1/s. Typical Value = 0.01.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::bp |
Droop (bp). Typical Value = 0.05.
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::dtc |
Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical Value = 390.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ka |
Minimum fuel flow (Ka). Typical Value = 0.23.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::kac |
Fuel system feedback (KAC). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::kca |
Acceleration control integral gain (Kca). Unit = 1/s. Typical Value = 100.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ksi |
Gain of radiation shield (Ksi). Typical Value = 0.8.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ky |
Coefficient of transfer function of fuel valve positioner (Ky). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::mnef |
Fuel flow maximum negative error value (MNEF). Typical Value = -0. 05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::mxef |
Fuel flow maximum positive error value (MXEF). Typical Value = 0.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::rcmn |
Minimum fuel flow (RCMN). Typical Value = -0.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::rcmx |
Maximum fuel flow (RCMX). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tac |
Fuel control time constant (Tac). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tc |
Compressor discharge volume time constant (Tc). Typical Value = 0.2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::td |
Temperature controller derivative gain (Td). Typical Value = 3.3.
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tfen |
Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical Value = 540.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tg |
Time constant of speed governor (Tg). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tsi |
Time constant of radiation shield (Tsi). Typical Value = 15.
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tt |
Temperature controller integration rate (Tt). Typical Value = 250.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ttc |
Time constant of thermocouple (Ttc). Typical Value = 2.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ty |
Time constant of fuel valve positioner (Ty). Typical Value = 0.2.