Public Attributes

IEC61970::Base::Domain::Float bca
 
IEC61970::Base::Domain::PU bp
 
IEC61970::Base::Domain::Temperature dtc
 
IEC61970::Base::Domain::PU ka
 
IEC61970::Base::Domain::Float kac
 
IEC61970::Base::Domain::Float kca
 
IEC61970::Base::Domain::Float ksi
 
IEC61970::Base::Domain::Float ky
 
IEC61970::Base::Domain::PU mnef
 
IEC61970::Base::Domain::PU mxef
 
IEC61970::Base::Domain::PU rcmn
 
IEC61970::Base::Domain::PU rcmx
 
IEC61970::Base::Domain::Seconds tac
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::Seconds td
 
IEC61970::Base::Domain::Temperature tfen
 
IEC61970::Base::Domain::Seconds tg
 
IEC61970::Base::Domain::Seconds tsi
 
IEC61970::Base::Domain::Temperature tt
 
IEC61970::Base::Domain::Seconds ttc
 
IEC61970::Base::Domain::Seconds ty
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Generic turbogas with acceleration and temperature controller.

Member Data Documentation

◆ bca

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::bca

Acceleration limit set-point (Bca). Unit = 1/s. Typical Value = 0.01.

◆ bp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::bp

Droop (bp). Typical Value = 0.05.

◆ dtc

IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::dtc

Exhaust temperature variation due to fuel flow increasing from 0 to 1 PU (deltaTc). Typical Value = 390.

◆ ka

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ka

Minimum fuel flow (Ka). Typical Value = 0.23.

◆ kac

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::kac

Fuel system feedback (KAC). Typical Value = 0.

◆ kca

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::kca

Acceleration control integral gain (Kca). Unit = 1/s. Typical Value = 100.

◆ ksi

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ksi

Gain of radiation shield (Ksi). Typical Value = 0.8.

◆ ky

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ky

Coefficient of transfer function of fuel valve positioner (Ky). Typical Value = 1.

◆ mnef

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::mnef

Fuel flow maximum negative error value (MNEF). Typical Value = -0. 05.

◆ mxef

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::mxef

Fuel flow maximum positive error value (MXEF). Typical Value = 0.05.

◆ rcmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::rcmn

Minimum fuel flow (RCMN). Typical Value = -0.1.

◆ rcmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::rcmx

Maximum fuel flow (RCMX). Typical Value = 1.

◆ tac

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tac

Fuel control time constant (Tac). Typical Value = 0.1.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tc

Compressor discharge volume time constant (Tc). Typical Value = 0.2.

◆ td

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::td

Temperature controller derivative gain (Td). Typical Value = 3.3.

◆ tfen

IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tfen

Turbine rated exhaust temperature correspondent to Pm=1 PU (Tfen). Typical Value = 540.

◆ tg

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tg

Time constant of speed governor (Tg). Typical Value = 0.05.

◆ tsi

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tsi

Time constant of radiation shield (Tsi). Typical Value = 15.

◆ tt

IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::tt

Temperature controller integration rate (Tt). Typical Value = 250.

◆ ttc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ttc

Time constant of thermocouple (Ttc). Typical Value = 2.5.

◆ ty

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST3::ty

Time constant of fuel valve positioner (Ty). Typical Value = 0.2.