#include <GovGAST1.h>
Modified single shaft gas turbine.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::a |
Turbine power time constant numerator scale factor (a). Typical Value = 0.8.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::b |
Turbine power time constant denominator scale factor (b). Typical Value = 1.
IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::db1 |
Intentional dead-band width (db1). Unit = Hz. Typical Value = 0.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::db2 |
Unintentional dead-band (db2). Unit = MW. Typical Value = 0.
IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::eps |
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::fidle |
Fuel flow at zero power output (Fidle). Typical Value = 0.18.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::gv1 |
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::gv2 |
Nonlinear gain point 2,PU gv (Gv2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::gv3 |
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::gv4 |
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::gv5 |
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::gv6 |
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::ka |
Governor gain (Ka). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::kt |
Temperature limiter gain (Kt). Typical Value = 3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::lmax |
Ambient temperature load limit (Lmax). Lmax is the turbine power output corresponding to the limiting exhaust gas temperature. Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::loadinc |
Valve position change allowed at fast rate (Loadinc). Typical Value = 0.05.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::ltrate |
Maximum long term fuel valve opening rate (Ltrate). Typical Value = 0.02.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::mwbase |
Base for power values (MWbase) (> 0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::pgv1 |
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::pgv2 |
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::pgv3 |
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::pgv4 |
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::pgv5 |
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::pgv6 |
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::r |
Permanent droop (R). Typical Value = 0.04.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::rmax |
Maximum fuel valve opening rate (Rmax). Unit = PU/sec. Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::t1 |
Governor mechanism time constant (T1). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::t2 |
Turbine power time constant (T2). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi- shaft engine, or with the compressibility of gas in the plenum of the free power turbine of an aero-derivative unit, for example. Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::t3 |
Turbine exhaust temperature time constant (T3). T3 represents delay in the exhaust temperature and load limiting system. Typical Value = 3.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::t4 |
Governor lead time constant (T4). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::t5 |
Governor lag time constant (T5). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::tltr |
Valve position averaging time constant (Tltr). Typical Value = 10.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::vmax |
Maximum turbine power, PU of MWbase (Vmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST1::vmin |
Minimum turbine power, PU of MWbase (Vmin). Typical Value = 0.