IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST Class Reference

#include <GovGAST.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU at
 
IEC61970::Base::Domain::PU dturb
 
IEC61970::Base::Domain::PU kt
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::PU r
 
IEC61970::Base::Domain::Seconds t1
 
IEC61970::Base::Domain::Seconds t2
 
IEC61970::Base::Domain::Seconds t3
 
IEC61970::Base::Domain::PU vmax
 
IEC61970::Base::Domain::PU vmin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Single shaft gas turbine.

Member Data Documentation

◆ at

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::at

Ambient temperature load limit (Load Limit). Typical Value = 1.

◆ dturb

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::dturb

Turbine damping factor (Dturb). Typical Value = 0.18.

◆ kt

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::kt

Temperature limiter gain (Kt). Typical Value = 3.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::mwbase

Base for power values (MWbase) (> 0).

◆ r

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::r

Permanent droop (R). Typical Value = 0.04.

◆ t1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::t1

Governor mechanism time constant (T1). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical Value = 0.5.

◆ t2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::t2

Turbine power time constant (T2). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi- shaft engine, or with the compressibility of gas in the plenum of a the free power turbine of an aero-derivative unit, for example. Typical Value = 0.5.

◆ t3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::t3

Turbine exhaust temperature time constant (T3). Typical Value = 3.

◆ vmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::vmax

Maximum turbine power, PU of MWbase (Vmax). Typical Value = 1.

◆ vmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::vmin

Minimum turbine power, PU of MWbase (Vmin). Typical Value = 0.