#include <GovGAST.h>
Single shaft gas turbine.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::at |
Ambient temperature load limit (Load Limit). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::dturb |
Turbine damping factor (Dturb). Typical Value = 0.18.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::kt |
Temperature limiter gain (Kt). Typical Value = 3.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::mwbase |
Base for power values (MWbase) (> 0).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::r |
Permanent droop (R). Typical Value = 0.04.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::t1 |
Governor mechanism time constant (T1). T1 represents the natural valve positioning time constant of the governor for small disturbances, as seen when rate limiting is not in effect. Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::t2 |
Turbine power time constant (T2). T2 represents delay due to internal energy storage of the gas turbine engine. T2 can be used to give a rough approximation to the delay associated with acceleration of the compressor spool of a multi- shaft engine, or with the compressibility of gas in the plenum of a the free power turbine of an aero-derivative unit, for example. Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::t3 |
Turbine exhaust temperature time constant (T3). Typical Value = 3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::vmax |
Maximum turbine power, PU of MWbase (Vmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST::vmin |
Minimum turbine power, PU of MWbase (Vmin). Typical Value = 0.