IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2 Class Reference

#include <GovCT2.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::Float aset
 
IEC61970::Base::Domain::PU db
 
IEC61970::Base::Domain::PU dm
 
IEC61970::Base::Domain::Frequency flim1
 
IEC61970::Base::Domain::Frequency flim10
 
IEC61970::Base::Domain::Frequency flim2
 
IEC61970::Base::Domain::Frequency flim3
 
IEC61970::Base::Domain::Frequency flim4
 
IEC61970::Base::Domain::Frequency flim5
 
IEC61970::Base::Domain::Frequency flim6
 
IEC61970::Base::Domain::Frequency flim7
 
IEC61970::Base::Domain::Frequency flim8
 
IEC61970::Base::Domain::Frequency flim9
 
IEC61970::Base::Domain::PU ka
 
IEC61970::Base::Domain::PU kdgov
 
IEC61970::Base::Domain::PU kigov
 
IEC61970::Base::Domain::PU kiload
 
IEC61970::Base::Domain::PU kimw
 
IEC61970::Base::Domain::PU kpgov
 
IEC61970::Base::Domain::PU kpload
 
IEC61970::Base::Domain::PU kturb
 
IEC61970::Base::Domain::PU ldref
 
IEC61970::Base::Domain::PU maxerr
 
IEC61970::Base::Domain::PU minerr
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::PU plim1
 
IEC61970::Base::Domain::PU plim10
 
IEC61970::Base::Domain::PU plim2
 
IEC61970::Base::Domain::PU plim3
 
IEC61970::Base::Domain::PU plim4
 
IEC61970::Base::Domain::PU plim5
 
IEC61970::Base::Domain::PU plim6
 
IEC61970::Base::Domain::PU plim7
 
IEC61970::Base::Domain::PU plim8
 
IEC61970::Base::Domain::PU plim9
 
IEC61970::Base::Domain::PU prate
 
IEC61970::Base::Domain::PU r
 
IEC61970::Base::Domain::Float rclose
 
IEC61970::Base::Domain::PU rdown
 
IEC61970::Base::Domain::Float ropen
 
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::DroopSignalFeedbackKind rselect = IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::DroopSignalFeedbackKind::_undef
 
IEC61970::Base::Domain::PU rup
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tact
 
IEC61970::Base::Domain::Seconds tb
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::Seconds tdgov
 
IEC61970::Base::Domain::Seconds teng
 
IEC61970::Base::Domain::Seconds tfload
 
IEC61970::Base::Domain::Seconds tpelec
 
IEC61970::Base::Domain::Seconds tsa
 
IEC61970::Base::Domain::Seconds tsb
 
IEC61970::Base::Domain::PU vmax
 
IEC61970::Base::Domain::PU vmin
 
IEC61970::Base::Domain::PU wfnl
 
IEC61970::Base::Domain::Boolean wfspd
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

General governor model with frequency-dependent fuel flow limit. This model is a modification of the GovCT1 model in order to represent the frequency- dependent fuel flow limit of a specific gas turbine manufacturer.

Member Data Documentation

◆ aset

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::aset

Acceleration limiter setpoint (Aset). Unit = PU/sec. Typical Value = 10.

◆ db

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::db

Speed governor dead band in per unit speed (db). In the majority of applications, it is recommended that this value be set to zero. Typical Value = 0.

◆ dm

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::dm

Speed sensitivity coefficient (Dm). Dm can represent either the variation of the engine power with the shaft speed or the variation of maximum power capability with shaft speed. If it is positive it describes the falling slope of the engine speed verses power characteristic as speed increases. A slightly falling characteristic is typical for reciprocating engines and some aero- derivative turbines. If it is negative the engine power is assumed to be unaffected by the shaft speed, but the maximum permissible fuel flow is taken to fall with falling shaft speed. This is characteristic of single-shaft industrial turbines due to exhaust temperature limits. Typical Value = 0.

◆ flim1

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim1

Frequency threshold 1 (Flim1). Unit = Hz. Typical Value = 59.

◆ flim10

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim10

Frequency threshold 10 (Flim10). Unit = Hz. Typical Value = 0.

◆ flim2

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim2

Frequency threshold 2 (Flim2). Unit = Hz. Typical Value = 0.

◆ flim3

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim3

Frequency threshold 3 (Flim3). Unit = Hz. Typical Value = 0.

◆ flim4

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim4

Frequency threshold 4 (Flim4). Unit = Hz. Typical Value = 0.

◆ flim5

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim5

Frequency threshold 5 (Flim5). Unit = Hz. Typical Value = 0.

◆ flim6

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim6

Frequency threshold 6 (Flim6). Unit = Hz. Typical Value = 0.

◆ flim7

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim7

Frequency threshold 7 (Flim7). Unit = Hz. Typical Value = 0.

◆ flim8

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim8

Frequency threshold 8 (Flim8). Unit = Hz. Typical Value = 0.

◆ flim9

IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::flim9

Frequency threshold 9 (Flim9). Unit = Hz. Typical Value = 0.

◆ ka

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::ka

Acceleration limiter Gain (Ka). Typical Value = 10.

◆ kdgov

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kdgov

Governor derivative gain (Kdgov). Typical Value = 0.

◆ kigov

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kigov

Governor integral gain (Kigov). Typical Value = 0.45.

◆ kiload

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kiload

Load limiter integral gain for PI controller (Kiload). Typical Value = 1.

◆ kimw

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kimw

Power controller (reset) gain (Kimw). The default value of 0.01 corresponds to a reset time of 100 seconds. A value of 0.001 corresponds to a relatively slow acting load controller. Typical Value = 0.

◆ kpgov

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kpgov

Governor proportional gain (Kpgov). Typical Value = 4.

◆ kpload

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kpload

Load limiter proportional gain for PI controller (Kpload). Typical Value = 1.

◆ kturb

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::kturb

Turbine gain (Kturb). Typical Value = 1.9168.

◆ ldref

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::ldref

Load limiter reference value (Ldref). Typical Value = 1.

◆ maxerr

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::maxerr

Maximum value for speed error signal (Maxerr). Typical Value = 1.

◆ minerr

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::minerr

Minimum value for speed error signal (Minerr). Typical Value = -1.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::mwbase

Base for power values (MWbase) (> 0). Unit = MW.

◆ plim1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim1

Power limit 1 (Plim1). Typical Value = 0.8325.

◆ plim10

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim10

Power limit 10 (Plim10). Typical Value = 0.

◆ plim2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim2

Power limit 2 (Plim2). Typical Value = 0.

◆ plim3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim3

Power limit 3 (Plim3). Typical Value = 0.

◆ plim4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim4

Power limit 4 (Plim4). Typical Value = 0.

◆ plim5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim5

Power limit 5 (Plim5). Typical Value = 0.

◆ plim6

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim6

Power limit 6 (Plim6). Typical Value = 0.

◆ plim7

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim7

Power limit 7 (Plim7). Typical Value = 0.

◆ plim8

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim8

Power limit 8 (Plim8). Typical Value = 0.

◆ plim9

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::plim9

Power Limit 9 (Plim9). Typical Value = 0.

◆ prate

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::prate

Ramp rate for frequency-dependent power limit (Prate). Typical Value = 0.017.

◆ r

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::r

Permanent droop (R). Typical Value = 0.05.

◆ rclose

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::rclose

Minimum valve closing rate (Rclose). Unit = PU/sec. Typical Value = -99.

◆ rdown

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::rdown

Maximum rate of load limit decrease (Rdown). Typical Value = -99.

◆ ropen

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::ropen

Maximum valve opening rate (Ropen). Unit = PU/sec. Typical Value = 99.

◆ rselect

IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::DroopSignalFeedbackKind IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::rselect = IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::DroopSignalFeedbackKind::_undef

Feedback signal for droop (Rselect). Typical Value = electricalPower.

◆ rup

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::rup

Maximum rate of load limit increase (Rup). Typical Value = 99.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::ta

Acceleration limiter time constant (Ta). Typical Value = 1.

◆ tact

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tact

Actuator time constant (Tact). Typical Value = 0.4.

◆ tb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tb

Turbine lag time constant (Tb). Typical Value = 0.1.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tc

Turbine lead time constant (Tc). Typical Value = 0.

◆ tdgov

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tdgov

Governor derivative controller time constant (Tdgov). Typical Value = 1.

◆ teng

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::teng

Transport time delay for diesel engine used in representing diesel engines where there is a small but measurable transport delay between a change in fuel flow setting and the development of torque (Teng). Teng should be zero in all but special cases where this transport delay is of particular concern. Typical Value = 0.

◆ tfload

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tfload

Load Limiter time constant (Tfload). Typical Value = 3.

◆ tpelec

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tpelec

Electrical power transducer time constant (Tpelec). Typical Value = 2.5.

◆ tsa

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tsa

Temperature detection lead time constant (Tsa). Typical Value = 0.

◆ tsb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::tsb

Temperature detection lag time constant (Tsb). Typical Value = 50.

◆ vmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::vmax

Maximum valve position limit (Vmax). Typical Value = 1.

◆ vmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::vmin

Minimum valve position limit (Vmin). Typical Value = 0.175.

◆ wfnl

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::wfnl

No load fuel flow (Wfnl). Typical Value = 0.187.

◆ wfspd

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovCT2::wfspd

Switch for fuel source characteristic to recognize that fuel flow, for a given fuel valve stroke, can be proportional to engine speed (Wfspd). true = fuel flow proportional to speed (for some gas turbines and diesel engines with positive displacement fuel injectors) false = fuel control system keeps fuel flow independent of engine speed. Typical Value = false.