#include <PFVArType2IEEEVArController.h>
Public Attributes | |
IEC61970::Base::Domain::Boolean | exlon |
IEC61970::Base::Domain::PU | ki |
IEC61970::Base::Domain::PU | kp |
IEC61970::Base::Domain::PU | qref |
IEC61970::Base::Domain::PU | vclmt |
IEC61970::Base::Domain::PU | vref |
IEC61970::Base::Domain::Float | vs |
![]() | |
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics * | ExcitationSystemDynamics |
![]() | |
IEC61970::Base::Domain::Boolean | enabled |
![]() | |
IEC61970::Base::Domain::String | aliasName |
IEC61970::Base::Domain::String | description |
IEC61970::Base::Domain::String | mRID |
IEC61970::Base::Domain::String | name |
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > | DiagramObjects |
The class represents IEEE VAR Controller Type 2 which is a summing point type controller. It makes up the outside loop of a two-loop system. This controller is implemented as a slow PI type controller, and the voltage regulator forms the inner loop and is implemented as a fast controller.
Reference: IEEE Standard 421.5-2005 Section 11.5.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::exlon |
Overexcitation or under excitation flag (EXLON) true = 1 (not in the overexcitation or underexcitation state, integral action is active) false = 0 (in the overexcitation or underexcitation state, so integral action is disabled to allow the limiter to play its role).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::ki |
Integral gain of the pf controller (KI).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::kp |
Proportional gain of the pf controller (KP).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::qref |
Reactive power reference (QREF).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::vclmt |
Maximum output of the pf controller (VCLMT).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::vref |
Voltage regulator reference (VREF).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEVArController::vs |
Generator sensing voltage (VS).