#include <OverexcLim2.h>
Public Attributes | |
IEC61970::Base::Domain::PU | ifdlim |
IEC61970::Base::Domain::PU | koi |
IEC61970::Base::Domain::PU | voimax |
IEC61970::Base::Domain::PU | voimin |
Public Attributes inherited from IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcitationLimiterDynamics | |
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics * | ExcitationSystemDynamics |
Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock | |
IEC61970::Base::Domain::Boolean | enabled |
Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject | |
IEC61970::Base::Domain::String | aliasName |
IEC61970::Base::Domain::String | description |
IEC61970::Base::Domain::String | mRID |
IEC61970::Base::Domain::String | name |
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > | DiagramObjects |
Different from LimIEEEOEL, LimOEL2 has a fixed pickup threshold and reduces the excitation set-point by mean of non-windup integral regulator. Irated is the rated machine excitation current (calculated from nameplate conditions: Vnom, Pnom, CosPhinom).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::ifdlim |
Limit value of rated field current (IFDLIM). Typical Value = 1.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::koi |
Gain Over excitation limiter (KOI). Typical Value = 0.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::voimax |
Maximum error signal (VOIMAX). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::voimin |
Minimum error signal (VOIMIN). Typical Value = -9999.