#include <ExcHU.h>
Hungarian Excitation System Model, with built-in voltage transducer.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::ae |
Major loop PI tag gain factor (Ae). Typical Value = 3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::ai |
Minor loop PI tag gain factor (Ai). Typical Value = 22.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::atr |
AVR constant (Atr). Typical Value = 2.19.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::emax |
Field voltage control signal upper limit on AVR base (Emax). Typical Value = 0. 996.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::emin |
Field voltage control signal lower limit on AVR base (Emin). Typical Value = - 0.866.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::imax |
Major loop PI tag output signal upper limit (Imax). Typical Value = 2.19.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::imin |
Major loop PI tag output signal lower limit (Imin). Typical Value = 0.1.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::ke |
Voltage base conversion constant (Ke). Typical Value = 4.666.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::ki |
Current base conversion constant (Ki). Typical Value = 0.21428.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::te |
Major loop PI tag integration time constant (Te). Typical Value = 0.154.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::ti |
Minor loop PI control tag integration time constant (Ti). Typical Value = 0. 01333.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcHU::tr |
Filter time constant (Tr). If a voltage compensator is used in conjunction with this excitation system model, Tr should be set to 0. Typical Value = 0.01.