#include <ExcELIN1.h>
Static PI transformer fed excitation system: ELIN (VATECH) - simplified model. This model represents an all-static excitation system. A PI voltage controller establishes a desired field current set point for a proportional current controller. The integrator of the PI controller has a follow-up input to match its signal to the present field current. A power system stabilizer with power input is included in the model.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::dpnf |
Controller follow up dead band (Dpnf). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::efmax |
Maximum open circuit excitation voltage (Efmax). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::efmin |
Minimum open circuit excitation voltage (Efmin). Typical Value = -5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::ks1 |
Stabilizer Gain 1 (Ks1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::ks2 |
Stabilizer Gain 2 (Ks2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::smax |
Stabilizer Limit Output (smax). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::tfi |
Current transducer time constant (Tfi). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::tnu |
Controller reset time constant (Tnu). Typical Value = 2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::ts1 |
Stabilizer Phase Lag Time Constant (Ts1). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::ts2 |
Stabilizer Filter Time Constant (Ts2). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::tsw |
Stabilizer parameters (Tsw). Typical Value = 3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::vpi |
Current controller gain (Vpi). Typical Value = 12.45.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::vpnf |
Controller follow up gain (Vpnf). Typical Value = 2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::vpu |
Voltage controller proportional gain (Vpu). Typical Value = 34.5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcELIN1::xe |
Excitation transformer effective reactance (Xe) (>=0). Xe represents the regulation of the transformer/rectifier unit. Typical Value = 0.06.