#include <ExcDC3A.h>
This is modified IEEE DC3A direct current commutator exciters with speed input, and death band. DC old type 4.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::edfmax |
Maximum voltage exciter output limiter (Efdmax). Typical Value = 99.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efd1 |
Exciter voltage at which exciter saturation is defined (Efd1). Typical Value = 2.6.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efd2 |
Exciter voltage at which exciter saturation is defined (Efd2). Typical Value = 3.45.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efdlim |
(Efdlim). true = exciter output limiter is active false = exciter output limiter not active. Typical Value = true.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efdmin |
Minimum voltage exciter output limiter (Efdmin). Typical Value = -99.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::exclim |
(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero not applied to integrator output. Typical Value = true.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::ke |
Exciter constant related to self-excited field (Ke). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::kr |
Death band (Kr). If Kr is not zero, the voltage regulator input changes at a constant rate if Verr > Kr or Verr < -Kr as per the IEEE (1968) Type 4 model. If Kr is zero, the error signal drives the voltage regulator continuously as per the IEEE (1980) DC3 and IEEE (1992, 2005) DC3A models. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::ks |
Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::kv |
Fast raise/lower contact setting (Kv). Typical Value = 0.05.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::seefd1 |
Exciter saturation function value at the corresponding exciter voltage, Efd1 (Se[Eefd1]). Typical Value = 0.1.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::seefd2 |
Exciter saturation function value at the corresponding exciter voltage, Efd2 (Se[Efd2]). Typical Value = 0.35.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::te |
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 1.83.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::trh |
Rheostat travel time (Trh). Typical Value = 20.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::vrmax |
Maximum voltage regulator output (Vrmax). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::vrmin |
Minimum voltage regulator output (Vrmin). Typical Value = 0.