#include <ExcAC5A.h>
Modified IEEE AC5A alternator-supplied rectifier excitation system with different minimum controller output.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::a |
Coefficient to allow different usage of the model (a). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::efd1 |
Exciter voltage at which exciter saturation is defined (Efd1). Typical Value = 5.6.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::efd2 |
Exciter voltage at which exciter saturation is defined (Efd2). Typical Value = 4.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::ka |
Voltage regulator gain (Ka). Typical Value = 400.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::ke |
Exciter constant related to self-excited field (Ke). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::kf |
Excitation control system stabilizer gains (Kf). Typical Value = 0.03.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::ks |
Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::seefd1 |
Exciter saturation function value at the corresponding exciter voltage, Efd1 (SE[Efd1]). Typical Value = 0.86.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::seefd2 |
Exciter saturation function value at the corresponding exciter voltage, Efd2 (SE[Efd2]). Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::ta |
Voltage regulator time constant (Ta). Typical Value = 0.02.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::tb |
Voltage regulator time constant (Tb). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::tc |
Voltage regulator time constant (Tc). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::te |
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 0.8.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::tf1 |
Excitation control system stabilizer time constant (Tf1). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::tf2 |
Excitation control system stabilizer time constant (Tf2). Typical Value = 0.8.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::tf3 |
Excitation control system stabilizer time constant (Tf3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::vrmax |
Maximum voltage regulator output (Vrmax). Typical Value = 7.3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC5A::vrmin |
Minimum voltage regulator output (Vrmin). Typical Value =-7.3.