IEC61970 16v29a - SINERGIEN 20170705
Public Attributes | List of all members
IEC61970::Base::Wires::PerLengthSequenceImpedance Class Reference

#include <PerLengthSequenceImpedance.h>

Inheritance diagram for IEC61970::Base::Wires::PerLengthSequenceImpedance:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Base::Wires::PerLengthSequenceImpedance:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::SusceptancePerLength b0ch
 
IEC61970::Base::Domain::SusceptancePerLength bch
 
IEC61970::Base::Domain::ConductancePerLength g0ch
 
IEC61970::Base::Domain::ConductancePerLength gch
 
IEC61970::Base::Domain::ResistancePerLength r
 
IEC61970::Base::Domain::ResistancePerLength r0
 
IEC61970::Base::Domain::ReactancePerLength x
 
IEC61970::Base::Domain::ReactancePerLength x0
 
- Public Attributes inherited from IEC61970::Base::Wires::PerLengthImpedance
std::list< IEC61970::Base::Wires::ACLineSegment * > ACLineSegments
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Sequence impedance and admittance parameters per unit length, for transposed lines of 1, 2, or 3 phases. For 1-phase lines, define x=x0=xself. For 2-phase lines, define x=xs-xm and x0=xs+xm.

Member Data Documentation

◆ b0ch

IEC61970::Base::Domain::SusceptancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::b0ch

Zero sequence shunt (charging) susceptance, per unit of length.

◆ bch

IEC61970::Base::Domain::SusceptancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::bch

Positive sequence shunt (charging) susceptance, per unit of length.

◆ g0ch

IEC61970::Base::Domain::ConductancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::g0ch

Zero sequence shunt (charging) conductance, per unit of length.

◆ gch

IEC61970::Base::Domain::ConductancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::gch

Positive sequence shunt (charging) conductance, per unit of length.

◆ r

IEC61970::Base::Domain::ResistancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::r

Positive sequence series resistance, per unit of length.

◆ r0

IEC61970::Base::Domain::ResistancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::r0

Zero sequence series resistance, per unit of length.

◆ x

IEC61970::Base::Domain::ReactancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::x

Positive sequence series reactance, per unit of length.

◆ x0

IEC61970::Base::Domain::ReactancePerLength IEC61970::Base::Wires::PerLengthSequenceImpedance::x0

Zero sequence series reactance, per unit of length.


The documentation for this class was generated from the following files: