IEC61970::Base::Wires::ExternalNetworkInjection Class Reference

#include <ExternalNetworkInjection.h>

Inheritance diagram for IEC61970::Base::Wires::ExternalNetworkInjection:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Base::Wires::ExternalNetworkInjection:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::ActivePowerPerFrequency governorSCD
 
IEC61970::Base::Domain::Boolean ikSecond
 
IEC61970::Base::Domain::CurrentFlow maxInitialSymShCCurrent
 
IEC61970::Base::Domain::ActivePower maxP
 
IEC61970::Base::Domain::ReactivePower maxQ
 
IEC61970::Base::Domain::Float maxR0ToX0Ratio
 
IEC61970::Base::Domain::Float maxR1ToX1Ratio
 
IEC61970::Base::Domain::Float maxZ0ToZ1Ratio
 
IEC61970::Base::Domain::CurrentFlow minInitialSymShCCurrent
 
IEC61970::Base::Domain::ActivePower minP
 
IEC61970::Base::Domain::ReactivePower minQ
 
IEC61970::Base::Domain::Float minR0ToX0Ratio
 
IEC61970::Base::Domain::Float minR1ToX1Ratio
 
IEC61970::Base::Domain::Float minZ0ToZ1Ratio
 
IEC61970::Base::Domain::ActivePower p
 
IEC61970::Base::Domain::ReactivePower q
 
IEC61970::Base::Domain::Integer referencePriority
 
IEC61970::Base::Domain::PU voltageFactor
 
- Public Attributes inherited from IEC61970::Base::Wires::RegulatingCondEq
IEC61970::Base::Domain::Boolean controlEnabled
 
IEC61970::Base::Wires::RegulatingControlRegulatingControl
 
- Public Attributes inherited from IEC61970::Base::Core::Equipment
IEC61970::Base::Domain::Boolean aggregate
 
IEC61970::Base::Domain::Boolean normallyInService
 
- Public Attributes inherited from IEC61970::Base::Core::PowerSystemResource
std::list< IEC61970::Base::Meas::Control * > Controls
 
std::list< IEC61970::Base::Meas::Measurement * > Measurements
 
IEC61970::Base::Core::PSRTypePSRType
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

This class represents external network and it is used for IEC 60909 calculations.

Member Data Documentation

◆ governorSCD

IEC61970::Base::Domain::ActivePowerPerFrequency IEC61970::Base::Wires::ExternalNetworkInjection::governorSCD

Power Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.

◆ ikSecond

IEC61970::Base::Domain::Boolean IEC61970::Base::Wires::ExternalNetworkInjection::ikSecond

Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik").

◆ maxInitialSymShCCurrent

IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::ExternalNetworkInjection::maxInitialSymShCCurrent

Maximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909

◆ maxP

IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::ExternalNetworkInjection::maxP

Maximum active power of the injection.

◆ maxQ

IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::ExternalNetworkInjection::maxQ

Not for short circuit modelling; It is used for modelling of infeed for load flow exchange. If maxQ and minQ are not used ReactiveCapabilityCurve can be used

◆ maxR0ToX0Ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::maxR0ToX0Ratio

Maximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance (R(0)/X(0) max). Used for short circuit data exchange according to IEC 60909

◆ maxR1ToX1Ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::maxR1ToX1Ratio

Maximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) max). Used for short circuit data exchange according to IEC 60909

◆ maxZ0ToZ1Ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::maxZ0ToZ1Ratio

Maximum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) max). Used for short circuit data exchange according to IEC 60909

◆ minInitialSymShCCurrent

IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::ExternalNetworkInjection::minInitialSymShCCurrent

Minimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909

◆ minP

IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::ExternalNetworkInjection::minP

Minimum active power of the injection.

◆ minQ

IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::ExternalNetworkInjection::minQ

Not for short circuit modelling; It is used for modelling of infeed for load flow exchange. If maxQ and minQ are not used ReactiveCapabilityCurve can be used

◆ minR0ToX0Ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::minR0ToX0Ratio

Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used for short circuit data exchange according to IEC 6090

◆ minR1ToX1Ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::minR1ToX1Ratio

Minimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) min). Used for short circuit data exchange according to IEC 60909

◆ minZ0ToZ1Ratio

IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::minZ0ToZ1Ratio

Minimum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) min). Used for short circuit data exchange according to IEC 60909

◆ p

IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::ExternalNetworkInjection::p

Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.

◆ q

IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::ExternalNetworkInjection::q

Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.

◆ referencePriority

IEC61970::Base::Domain::Integer IEC61970::Base::Wires::ExternalNetworkInjection::referencePriority

Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.

◆ voltageFactor

IEC61970::Base::Domain::PU IEC61970::Base::Wires::ExternalNetworkInjection::voltageFactor

Voltage factor in pu, which was used to calculate short-circuit current Ik" and power Sk".