#include <TransformerObservation.h>
Public Attributes | |
IEC61970::Base::Domain::Temperature | bushingTemp |
IEC61970::Base::Domain::String | dga |
IEC61970::Base::Domain::String | freqResp |
IEC61970::Base::Domain::String | furfuralDP |
IEC61970::Base::Domain::Temperature | hotSpotTemp |
IEC61970::Base::Domain::String | oilColor |
IEC61970::Base::Domain::Voltage | oilDielectricStrength |
IEC61970::Base::Domain::String | oilIFT |
IEC61970::Base::Domain::String | oilLevel |
IEC61970::Base::Domain::String | oilNeutralizationNumber |
IEC61970::Base::Domain::String | pumpVibration |
IEC61968::Common::Status | status |
IEC61970::Base::Domain::Temperature | topOilTemp |
IEC61970::Base::Domain::String | waterContent |
IEC61970::Base::Wires::TransformerTank * | Transformer |
std::list< IEC61968::InfIEC61968::InfAssets::WindingInsulation * > | WindingInsulationPFs |
Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject | |
IEC61970::Base::Domain::String | aliasName |
IEC61970::Base::Domain::String | description |
IEC61970::Base::Domain::String | mRID |
IEC61970::Base::Domain::String | name |
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > | DiagramObjects |
Common information captured during transformer inspections and/or diagnostics. Note that some properties may be measured through other means and therefore have measurement values in addition to the observed values recorded here.
IEC61970::Base::Domain::Temperature IEC61968::InfIEC61968::InfAssets::TransformerObservation::bushingTemp |
Bushing temperature.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::dga |
Dissolved Gas Analysis. Typical values are: Acceptable, Overheating, Corona, Sparking, Arcing.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::freqResp |
Frequency Response Analysis. Typical values are: acceptable, slight movement, significant movement, failed, near failure. A graphic of the response diagram, which is a type of document, may be associated with this analysis through the recursive document relationship of the ProcedureDataSet.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::furfuralDP |
Overall measure of furfural in oil and mechanical strength of paper. DP, the degree of polymerization, is the strength of the paper. Furfural is a measure of furfural compounds, often expressed in parts per million.
IEC61970::Base::Domain::Temperature IEC61968::InfIEC61968::InfAssets::TransformerObservation::hotSpotTemp |
Hotspot oil temperature.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::oilColor |
Oil Quality Analysis-Color.
IEC61970::Base::Domain::Voltage IEC61968::InfIEC61968::InfAssets::TransformerObservation::oilDielectricStrength |
Oil Quality Analysis-Dielectric Strength.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::oilIFT |
Oil Quality Analysis- inter facial tension (IFT) - number-Dynes/CM.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::oilLevel |
The level of oil in the transformer.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::oilNeutralizationNumber |
Oil Quality Analysis-Neutralization Number - Number - Mg KOH.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::pumpVibration |
Pump vibration, with typical values being: nominal, high.
IEC61970::Base::Domain::Temperature IEC61968::InfIEC61968::InfAssets::TransformerObservation::topOilTemp |
Top oil temperature.
IEC61970::Base::Domain::String IEC61968::InfIEC61968::InfAssets::TransformerObservation::waterContent |
Water Content expressed in parts per million.